SECTION 2 – INSTALLATION
LOCATION AND CLEARANCES
Use the following guidelines to select a suitable loca-
tion for the unit installation:
• The unit is designed for indoor installation only.
• Verify the floor or foundation is level. For proper
unit operation the unit should be level within a
1/16" side to side and 1/8" front to back tolerance.
Failure to level the unit properly could result in
condensate management problems, such as stand-
ing water inside the unit.
Freezing Damage Caution Label
See Figure 1 for cautionary information on not storing
units in areas that experience below freezing condi-
tions.
not
24 inch clearance required
on standard units, 3 inch
clearance required on units
with low clearance option.
18 inch
Clearance
Optional when clear-
ance is available.
Removable doors
with hinges. One door
handle and one tool-
operated latch.
"A"
24 inch clearance required
on standard units, 3 inch
clearance required on units
with low clearance option.
NO.
1
2
4 inch prefilter + 4 inch high efficiency filter
FIGURE 2 - RECOMMENDED SERVICE AND MAINTENANCE CLEARANCE, TOP DISCHARGE
(LSW_025–040)
12
LEFT
FILTER OPTIONS
4 inch filter
FIGURE 1 - CAUTION LABEL
Removable inner panel is provided
for access to water valves when no
left side clearance is required.
REAR
FILTER SECTION
COIL SECTION
FAN
SECTION
FRONT
78.37
inch
"A"
76.43
80.68
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
Removable door with hinges.
One door handle and tool
operated latch.
Electrical panel door (over).
RIGHT
Non removable with hinges.
One door handle and tool
operated latch.
Entry door (under),
standard 32 inch wide x
44 inch high nominal with
one door handle and tool
operated latch.
42 inch
Clearance
075-83768-903 REV-
NOTE:
1. All dimensions are in inches.
JOHNSON CONTROLS