ENGINEERING GUIDE FORM 145.05-EG2 (618) Water-Cooled Self-Contained Units L-Series, Vertical...
Page 2
095 = 95 Ton POWER SUPPLY CONNECTION H - High Temperature 105 = 105 Ton SPT = Single Point Terminal Block SPD = Single Point Disconnect Switch DPT = Dual Point Terminal Block DPD = Dual Point Disconnect Switch JOHNSON CONTROLS...
FEATURES AND OPTIONS ............................ 11 SELECTION PROCEDURE ............................15 OPERATING LIMITATIONS ............................18 PHYSICAL DATA ..............................19 COOLING PERFORMANCE DATA ........................22 DIMENSIONAL DATA .............................33 AIR PRESSURE DROPS ............................57 SUPPLY FAN DATA ..............................63 WATER PRESSURE DROP ............................65 ELECTRICAL DATA ...............................68 OPERATING WEIGHTS ............................69 GUIDE SPECIFICATIONS ............................71 JOHNSON CONTROLS...
Page 4
FORM 145.05-EG2 (618) THIS PAGE INTENTIONALLY LEFT BLANK. JOHNSON CONTROLS...
• Evaporator coil circuiting supports low leaving air temperature designs to reduce design air flow and reduce fan operating energy. • High efficiency evaporator coil available for lower air flow, low leaving air tempera- ture applications. JOHNSON CONTROLS...
Page 6
• Multiple scroll compressors, due to their smoother flow and stepped operation, mini- mize the sound associated with the refrigerant system. • The compressors are located out side air stream, including all the refrigerant piping and condenser water piping. JOHNSON CONTROLS...
Page 7
• Minimum class II fans for high static requirements. Class III fans available. • Supply fan and motor assembly is isolated with springs to minimize the vibration and sound transmission to the rest of the unit and beyond. • Bearing lubrication line brought to one location for easy maintenance. JOHNSON CONTROLS...
Page 8
• Water economy coil with optional mechanically cleanable return bends is available. • Condenser water flow through the unit is enabled only in cooling mode. Minimum condenser water temperature for unit compressor operation in this mode is 40.0°F. JOHNSON CONTROLS...
Page 9
Various sections are as follows: • Refrigerant and heating section consisting of evaporator coil, water economy coil, condensers, compressors, condenser water piping, and heating options. JOHNSON CONTROLS...
Page 10
Different control options: • Dry bulb • Single enthalpy • Dual enthalpy • Inlet sound attenuating plenum attaches to the filter section for further reducing the sound emitted through the unit air inlet. JOHNSON CONTROLS...
Table 19 and Table 20 on page 57. 12. With all options selected, add air pressure drops of all the components selected, in- cluding evaporator coil, to external static pressure required to determine total static pressure required for the supply air fan. JOHNSON CONTROLS...
Page 16
18. The component weights are in Table 30 on page 69 and Table 31 on page 70. Add weights of the components covered by the options selected. To obtain operat- ing weight, add water weights corresponding to the option selected carrying water weights. JOHNSON CONTROLS...
Page 17
0.914 0.899 0.944 0.934 0.973 0.968 1.000 1.000 1.026 1.031 1.052 1.061 1.076 1.090 1.100 1.118 TABLE 3 - HOT WATER HEATING CORRECTION FACTORS AIR FLOW PERCENT TOTAL CAPACITY 0.903 0.929 0.953 0.977 1.000 1.020 1.042 1.061 1.082 JOHNSON CONTROLS...
90.0°F Entering Cond. Water Temp with Condenser 40.0°F 90.0°F Water Control Valve Entering Cond. Water Temp w/o Condenser 60.0°F 90.0°F Water Control Valve Steam Heat-Steam Pressure 5 psig 15 psig Hot Water Heat Entering Water Temp 140.0°F 160.0°F JOHNSON CONTROLS...
FORM 145.05-EG2 (618) Dimensional Data OVERVIEW OF COMBINED UNIT LSWU025–040 MODELS JOHNSON CONTROLS...
Page 34
FORM 145.05-EG2 (618) Dimensional Data (Cont’d) OVERVIEW OF SPLIT SHIPMENT LSWU025–040 MODELS JOHNSON CONTROLS...
Page 35
FORM 145.05-EG2 (618) OVERVIEW OF SERVICE CLEARANCES LSWU025–040 MODELS JOHNSON CONTROLS...
Page 36
SOUND-ATTENUATING PLENUM SHIPS SEPARATELY FROM BASE UNIT SEGMENT(S). 66.09 OPTION IS NOT AVAILABLE WITH DUCTED CONNECTIONS. WITH THIS OPTION THE TOP ROW OF FILTERS CAN ONLY BE 5.95 REMOVED FROM THE END OF THE FILTER RACK. 23.94 JOHNSON CONTROLS OPTIONAL SOUND-ATTENUATING (INLET) PLENUM OPTION...
Page 37
FORM 145.05-EG2 (618) SOUND ATTENUATING PLENUM SERVICE CLEARANCE LSWU025–040 MODELS JOHNSON CONTROLS...
Page 38
4" PRE-FILTER + 4" HIGH EFFICIENCY FILTER 80.68 114.90 "A" COIL SECTION *MINIMUM INTERIOR DUCT DIMENSIONS ("B") FILTER SECTION 26.47* AIRSIDE ECONOMIZER 34.22 3.86* 55.47* 9.26* 74.06 2.00 NOTE: AIRSIDE ECONOMIZER WILL BE SHIPPED SEPARATELY 55.47* 11.51* 26.47* 78.32 43.41* JOHNSON CONTROLS...
Page 39
FORM 145.05-EG2 (618) AIRSIDE ECONOMIZER SERVICE CLEARANCES LSWU025–040 MODELS JOHNSON CONTROLS...
Page 40
FORM 145.05-EG2 (618) Dimensional Data (Cont’d) MOUNTING PAD LOCATIONS LSWU025–040 MODELS REAR FILTER SECTION COIL SECTION MOUNTING LOCATIONS 35.00 LEFT FAN SECTION RIGHT 70.13 FRONT JOHNSON CONTROLS...
Page 41
FORM 145.05-EG2 (618) OVERVIEW OF COMBINED UNIT LSWU050–060 MODELS JOHNSON CONTROLS...
Page 42
FORM 145.05-EG2 (618) Dimensional Data (Cont’d) OVERVIEW OF SPLIT SHIPMENT LSWU050–060 MODELS JOHNSON CONTROLS...
Page 43
FORM 145.05-EG2 (618) OVERVIEW OF SERVICE CLEARANCES LSWU050–060 MODELS JOHNSON CONTROLS...
Page 44
SOUND-ATTENUATING PLENUM SHIPS SEPARATELY FROM BASE UNIT SEGMENT(S). 85.59 OPTION IS NOT AVAILABLE WITH DUCTED CONNECTIONS WITH THIS OPTION THE TOP ROW OF FILTERS CAN ONLY BE 23.91 7.86 REMOVED FROM THE END OF THE FILTER RACK. JOHNSON CONTROLS OUND-ATTENUATING (INLET) PLENUM...
Page 45
FORM 145.05-EG2 (618) SOUND ATTENUATING PLENUM SERVICE CLEARANCES LSWU050–060 MODELS JOHNSON CONTROLS...
Page 46
4" PRE-FILTER + 4" HIGH EFFICIENCY FILTER 86.25 120.47 *MINIMUM INTERIOR DUCT DIMENSIONS FAN SECTION "A" ("B") COIL SECTION FILTER SECTION 26.47* 34.22 AIRSIDE ECONOMIZER 75.47* 8.26* 3.86* 92.06 2.97 NOTE: AIRSIDE ECONOMIZER WILL BE SHIPPED SEPARATELY 75.47* 11.49* 26.47* 88.80 53.89* JOHNSON CONTROLS...
Page 47
FORM 145.05-EG2 (618) AIRSIDE ECONOMIZER SERVICE CLEARANCES LSWU050–060 MODELS JOHNSON CONTROLS...
Page 48
FORM 145.05-EG2 (618) Dimensional Data (Cont’d) MOUNTING PAD LOCATIONS LSWU050–060 MODELS REAR FILTER SECTION MOUNTING 14X 2.00 COIL SECTION LOCATIONS 14X 6.00 RIGHT 35.12 FAN SECTION LEFT 75.75 FRONT JOHNSON CONTROLS...
Page 49
FORM 145.05-EG2 (618) OVERVIEW OF COMBINED UNIT LSWU070–105 MODELS JOHNSON CONTROLS...
Page 50
FORM 145.05-EG2 (618) Dimensional Data (Cont’d) OVERVIEW OF SPLIT SHIPMENTS LSWU070–105 MODELS JOHNSON CONTROLS...
Page 51
FORM 145.05-EG2 (618) OVERVIEW OF SERVICE CLEARANCES LSWU070–105 MODELS JOHNSON CONTROLS...
Page 52
4" PRE-FILTER + 4" HIGH EFFICIENCY FILTER 106.31 OPTION IS NOT AVAILABLE WITH DUCTED CONNECTIONS WITH THIS OPTION THE TOP ROW OF FILTERS CAN ONLY BE OPTIONAL SOUND-ATTENUATING (INLET) PLENUM REMOVED FROM THE END OF THE FILTER RACK. JOHNSON CONTROLS NOTES: SOUND-ATTENUATING PLENUM OPTION CAN BE COMBINED...
Page 53
FORM 145.05-EG2 (618) SOUND ATTENUATING PLENUM SERVICE CLEARANCE LSWU070–105 MODELS JOHNSON CONTROLS...
Page 54
4" PRE-FILTER + 4" HIGH EFFICIENCY FILTER 106.31 156.53 *MINIMUM INTERIOR DUCT DIMENSIONS FAN SECTION "A" COIL SECTION ("B") FILTER SECTION 35.47* 50.22 AIRSIDE ECONOMIZER 7.36* 101.47* 8.26* 118.00 4.25 NOTE: AIRSIDE ECONOMIZER WILL BE SHIPPED SEPARATELY 101.47* 12.52* 35.47* 100.99 55.04* JOHNSON CONTROLS...
Page 55
FORM 145.05-EG2 (618) AIRSIDE ECONOMIZER SERVICE CLEARANCES LSWU070–105 MODELS JOHNSON CONTROLS...
Page 56
FORM 145.05-EG2 (618) Dimensional Data (Cont’d) MOUNTING PAD LOCATIONS LSWU070–105 MODELS REAR FILTER SECTION MOUNTING COIL SECTION LOCATIONS 10X 2.00 LEFT LEFT 10X 6.00 RIGHT 52.00 (SPLIT LINE AT FLOOR ELEVATION) FAN SECTION 96.00 FRONT JOHNSON CONTROLS...
Condenser Water PD Water Economizer PD (when ac ve) Condenser + Water Econ PD Water Flow (GPM) LSWU050-060 Water Pressure Drop Condenser Water PD Water Economizer PD (when ac ve) Condenser + Water Econ PD Water Flow (GPM) JOHNSON CONTROLS...
Page 66
Water Economizer PD (when ac ve) Condenser + Water Econ PD 1.00 Water Flow (GPM) LSWU095-105 Water Pressure Drop 100.00 Condenser Water PD 10.00 Water Economizer PD (when ac ve) Condenser + Water Econ PD 1.00 Water Flow (GPM) JOHNSON CONTROLS...
Page 67
FORM 145.05-EG2 (618) HOT WATER PRESSURE DROPS (INCHES W.C.) LSWU025-040 Hot Water Pressure Drop Water Flow (GPM) LSWU050-060 Hot Water Pressure Drop Water Flow (GPM) LSWU070-105 Hot Water Pressure Drop 100.00 10.00 1.00 Water Flow (GPM) JOHNSON CONTROLS...
12 fins per inch. An adjustable thermal expansion valve (TXV) including an external equalizer shall feed each circuit. The TXV shall be sized to operate with mini- mum entering condenser water temperatures of 55.0°F. The coil shall be leak tested with high-pressure nitrogen in a warm water bath. JOHNSON CONTROLS...
Page 72
[A non-averaging type freezestat shall be factory installed. When the freezestat senses the entering air temperature is below the set point, the unit shall be put into the unoccupied mode and the economizer valve shall be driven to 100% open and the condenser valve shall be driven closed.] JOHNSON CONTROLS...
Page 73
Bearing diameter shall be the same size as the main shaft diameter. Bearings shall be sized to pro- vide an L-50 life at 200,000 hours. The fan bearings shall have extended grease lines to a common location. JOHNSON CONTROLS...
Page 74
Each compres- sor will have individual refrigerant circuit. Compressor RLA will not exceed 21.2 Amps at 460 Volts or 47 Amps at 208 Volts. Compressors shall be 15 nominal horsepower or lower. JOHNSON CONTROLS...
Page 75
• Supply Air Temperature Reset via VFD Speed (variable air volume (VAV) only) • Supply Air Temperature Reset Limits Safeties • Low Suction Pressure (1 per compressor) • High Discharge Pressure (1 per compressor) • Compressor Motor Overload (1 per compressor) • Supply Fan Fail • Low Entering Air Temperature JOHNSON CONTROLS...
Page 76
• Return Air Humidity Sensor Failure (Units with Airside Economizer) • Duct Pressure Transducer Failure • Low Water Flow (Units with Water Flow Switch) • Low Water Temperature • Entering Water Temperature Sensor Failure • Leaving Water Temperature Sensor Failure JOHNSON CONTROLS...
Page 77
1. Waterside Economizer with Adjustable Approach setpoint 2. Airside Dry Bulb (Units Equipped with Mixing Box) 3. Airside Single Enthalpy (Units Equipped with Mixing Box) 4. Airside Dual Enthalpy (Units Equipped with Mixing Box) Note: Economizer sequences allow for economizing with mechanical cooling when JOHNSON CONTROLS...
Page 78
The valve actuator shall be controlled through the factory installed main unit control system to maintain refrigerant head pres- sure by reducing the water flow as necessary to allow proper functioning of thermostatic JOHNSON CONTROLS...
Page 79
Service Clearance requirements on all four sides shall be indicated clearly on the submit- tal drawings. Optionally, Unit shall require NO MORE THAN 3 inches of clearance on two sides so that the unit may be placed in a corner. JOHNSON CONTROLS...
Page 80
Duct openings for the discharge plenum shall not require field cutting or modifications. The discharge plenum shall be constructed of formed 16-gauge pre-painted galvanized steel. The exterior panels shall be fabricated from 18-gauge pre-painted galvanized steel. JOHNSON CONTROLS...
Page 81
20-gauge galvanized steel perforated metal liner. The plenum shall be available on the units without low service clearance units. This option is available only when airside economizer is not chosen. JOHNSON CONTROLS...