SECTION 6 – USER INTERFACE CONTROL CENTER

TABLE 42 - BACNET MS/TP, MODBUS, BACNET IP

BACNET
USER INTERFACE
NAME
NAME
ACT _DSP_
Duct Static Setpoint
SP
ACT_MIN_
Active Minimum
POS
Position
ACT_SAT_
Supply Air Setp
SP
ACT_SLAB_
Active Slab Control
CTL
ALARM
Alarm
AMORN_
Adapt Morn Warm Up
WA_ACT
Active
AV_PRS_A_
Avg Press Suction A
SUC
AV_PRS_DIS Avg Press Discharge A
BYPASS_
Bypass Damper
DAMPER
BYP_VALV_
Bypass Valve Position
POS
COMFORT_
Comfort Ventilation
VENT
COMP_A
Compressor A
COMP_B
Compressor B
COMP_C
Compressor C
COMP_D
Compressor D
COMP_E
Compressor E
COMP_F
Compressor F
COMP_A_
Compressor A Load
LOAD
COMP_A_
Compressor 1A Oper
OPER
Hrs
COMP_B_
Compressor 1B Oper
OPER
Hrs
COMP_C_
Compressor 2A Oper
OPER
Hrs
COMP_D_
Compressor 2B Oper
OPER
Hrs
COMP_E_
Compressor 3A Oper
OPER
Hrs
COMP_F_
Compressor 3B Oper
OPER
Hrs
172
BACNET
MODBUS
READ/
OBJECT
REGISTER
WRITE
TYPE AND
ADDRESS
INSTANCE
R
AI01
514
R
AI03
516
R
AI04
517
R/W
AI5
1102
R
BI02
1283
R
BI01
1282
R
AI5
518
R
AI2
515
R
AI06
519
R
AI64
577
R/W
AI2
1103
R
BI03
1284
R
BI04
1285
R
BI05
1286
R
BI06
1287
R
BI07
1288
R
BI08
1289
R
AI15
528
R
AI09
522
R
AI10
523
R
AI11
524
R
AI12
525
R
AI13
526
R
AI14
527
ISSUE DATE: 10/31/2019
POINTS LIST DESCRIPTION
A Derived Value the Duct Static is Controlled
to ("WG)
A Derived Value the Damper is Controlled to
for Minimum Ventilation Air (%)
A Derived Value the Supply Air Temperature
is Controlled to (F)
Allows the Active Slab Control Feature to be
Turned On and Off on FlexSys Units (0 = Off
/ 1 = On)
Gives the Status of the Alarm (NFL - No
Fault; FLT - Faulted)
Identifies when Adaptive Morning Warm Up
is Active (Off / On)
Gives the Average Suction Pressure for the
System A Unloading Compressor
Gives the Average Discharge Pressure for
the System A Unloading Compressor
Actual Bypass Damper Position (%)
The Analog Output from the Control to the
Bypass Valve
Gives the Status of the Comfort Vent Option
and Allows it to be Turned On and Off (0 =
Off; 1 = On)
Status of Compressor A, (On/Off)
Status of Compressor B, (On/Off)
Status of Compressor C, (On/Off)
Status of Compressor D, (On/Off)
Status of Compressor E, (On/Off)
Status of Compressor F, (On/Off)
Gives the Status of the Unloading Compres-
sor in %.
The Number of Hours Compressor A has
been in Operation (Hour)
The Number of Hours Compressor B has
been in Operation (Hour)
The Number of Hours Compressor C has
been in Operation (Hour)
The Number of Hours Compressor D has
been in Operation (Hour)
The Number of Hours Compressor E has
been in Operation (Hour)
The Number of Hours Compressor F has
been in Operation (Hour)
JOHNSON CONTROLS
FORM 145.05-NOM7