Teaching The Switching Points In Teach Mode; Measuring Volume Manually In Recorder Mode - Festo SFAB-PNLK Series Operating Instruction

Flow sensor
Table of Contents

Advertisement

Commissioning
7.4

Teaching the switching points in TEACH mode

The switching points for flow monitoring can be established in the TEACH mode è 4.2.3 Switching
outputs.
Before the teach-in, set the switching function to EDIT mode è 7.3 Configuring the sensor in EDIT
mode.
The procedure for teaching the OutA or OutB switching signal is the same in principle:
– OutA: press the [A] key.
– OutB: press the [B] key.
In the following, the procedure for the switching signal OutA is described.
Requirement: the sensor is ready for operation and is in RUN mode.
1. Generate the flow rate for TP1.
2. Press the [A] key and the [Edit] key.
Ä With security code activated: [Lock] flashes.
3. Set the security code with the [A] or [B] key.
4. Press the [Edit] key.
Ä 't-IN' flashes.
Ä The measured value will then be applied as teach point (TP1).
5. Generate the flow rate for TP2.
6. Press the [A] key and the [Edit] key.
Ä The measured value will then be applied as teach point (TP2).
Ä The 'SP' switching point of the 'SP.Lo' and 'SP.Hi' switching points become valid.
Ä The RUN mode is displayed.
7.5

Measuring volume manually in RECORDER mode

Requirement: the sensor is ready for operation and is in RUN mode.
1. Press the [A] and [B] keys simultaneously.
Ä The current status of the measurement is displayed.
2. To start or stop the measurement, press the [A] key.
3. To reset the measurement, press the [B] key.
4. To exit RECORDER mode, press the [A] and [B] key simultaneously.
Ä The RUN mode is displayed.
If the RECORDER mode is exited during a volume measurement, the measurement will continue in the
background.
If the operating voltage is switched off, the measurement is aborted without saving the value.