SFAH
Master sensor
Fig. 16 Example of port assignment SFAH-...M8
1. Select special menu [Spec] at the master sensor via device settings.
2. Press the Edit button briefly until [MASt] appears.
3. With A or B key, select [ON].
4. Press the Edit button.
è [REPL] / [RedY] appears.
5. Press A- or B-key.
è [REPL] / [RUN] appears briefly.
è The parameters are transmitted to the device sensor.
è [REPL] / [RedY] appears. If an error occurs, an error message appears (è Tab. 30).
6. Repeat point 5 if an additional sensor should be parameterised.
7. Press the Edit button.
è Switch to the RUN mode.
8.11

Configure sensor (EDIT mode)

Fig. 17 shows the complete menu structure. Some menu options or setting values are not applicable,
depending on the product variant and the selected switching function.
8.12

Teach switching points (TEACH mode)

Note
If [Lock] [IOL] appears on the display, the sensor is blocked through the IO-Link Device Access Lock
and can only be parameterised via IO-Link.
Note
The process for Teach is the same for configuring the switching outputs for OutA and OutB.
• For teaching-in OutA: A-key + Edit button
• For teaching-in OutB: B-key + Edit button
In the following, the process is described using the switching output OutA.
The Teach function is only available for flow monitoring.