6
RECOVERY MENU
6.1 ENABLING RECOVERY
WARNING: this mask is available on units with total recovery.
This mask is used to display the actual status of the total recovery, and to enable or
disable the total recovery:
O General
Switch On:
YES
The mask displays the total recovery status;the available options are:
— flow switch open (water is not circulating in the hydraulic circuit of the recovery
system and therefore it is disabled);
— enabled (water is circulating in the hydraulic circuit of the recovery system and
therefore it is enabled);
— general off (whole unit in stand-by);
— off from display (general disabling of the unit from the pGD1 button);
Enable: allows to enable or disable the total recovery;
6.2 SET THE RECOVERY SET VALUE
WARNING: this mask is available on units with total recovery.
This mask allows to view and set the value to be assigned to the recovery work set
(default value 45° C, setting range 30~50° C):
Setpoint 1:
45.0°C
23