CONNECT THE CABLE TO
THE INDOOR UNIT
Attention!
Electric safety regulations for the
initial Installation
If there is serious safety problem
about the power supply, the
technicians should refuse to install
the air conditioner and explain to the
client until the problem is solved.
Power voltage should be in the
range of 90%~110%of rated
voltage.
The creepage protector and main
power switch with a 1.5 times
capacity of Max. Current of the unit
should be installed in power circuit.
Ensure the air conditioner is
grounded well.
According to the attached Electrical
Connection Diagram located on the
panel of the outdoor unit to connect
the wire.
All wiring must comply with local and
national electrical codes and be
installed by qualified and skilled
electricians.
An individual branch circuit and
single receptacle used only for this
air conditioner must be available.
See the following table for
suggested wire sizes and fuse
specifications.
Minimum nominal cross-sectional
area of conductors
Nominal cross-
Rated current
of appliance
(A)
> 3 и
6
> 6 и
10
> 10 и
16
> 16 и
25
Note!
The cable size and the current of
the fuse or switch are determined by
the maximum current indicated on the
nameplate which located on the side
panel of the unit. Please refer to the
nameplate before selecting the cable,
fuse and switch.
sectional
area
2
(mm )
0,75
1.0
1,5
2,5