2.4 Location, Mounting And Cooling

This power supply is fan cooled. The air intake is at the front panel and the exhaust is at
the rear panel. Upon installation allow cooling air to reach the front panel ventilation inlets.
Allow minimum 10cm (4Inch) of unrestricted air space at the front and the rear of the unit.
The power supply should be used in an area that the ambient temperature does not exceed
+50ºC.

2.5 AC Source Requirements

The D750 can be operated from a nominal 85V to 265V, single phase, 47~63Hz. The input
voltage range and current required for each model is specified in Chapter 2. Ensure that
under heavy load, the AC voltage supplied to the power supply does not fall below the
specifications described in Section 1.3.

2.6 AC Input Power Connection

Connection of this power supply to an AC power source should be made by an electrician
There is a potential shock hazard if the power supply chassis (with cover in place) is not
connected to an electrical safety ground via the safety ground in the AC input connector.
Some components inside the power supply are at AC voltage even when the On/Off switch
is in the "Off" position. To avoid electric shock hazard, disconnect the line cord and load

2.6.1 AC Input Connector

The rear panel can be connected to AC power through AC and Euroblocks, and the ground
wire must be connected to ground for safe grounding.

2.6.2 AC Input Cord

The AC input cord and ground wire size must be No. 12 AWG or larger. The AC input cord
14
│ www.deltaww.com
CAUTION
or other qualified personnel.
WARNING
WARNING
and wait two minutes before removing cover.
WARNING
must be no longer than 3m.