TECHNICAL DATASHEET
Sync DIN Rail Power Supply
24V 30W 1 Phase (NEC Class 2) / DRS-24V30W1NZ
General Description
The ultra-compact and competitively priced Delta Sync DIN rail power supply series is designed for industrial applications requiring
highly reliable power supply within a tight space. The Sync series operates with universal AC input range and offers full power up to
55°C. The output is adjustable from 24-28 volts, and can support up to 3000 microfarads of load capacitance. A green LED indicates
output is present. All models in the series are certified according to IEC/EN/UL 60950-1 Information Technology Equipment (ITE),
IEC/EN/UL 62368-1 Audio/video, information and communication technology equipment and UL 508 Industrial Control Equipment
(ICE). The series is also fully compliant with RoHS Directive 2011/65/EU for environmental protection. NEC Class 2 and Limited Power
Source (LPS) approvals are available for this product.
Model Information
Sync DIN Rail Power Supply
Model Number
DRS-24V30W1NZ
Model Numbering
DR
S –
DIN Rail
Product Series
S – Sync Series
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
1
www.DeltaPSU.com (July 2019, Rev. 04)
Input Voltage Range
85-264Vac (120-375Vdc)
24V
30W
Output Voltage
Output Power
Highlights & Features
Ultra compact size and galvanic isolation up to 3.0KVac
between input to output and input to ground
Universal AC input voltage and full power from -10°C to
+55°C operation
Up to 88.0% efficiency
Low earth leakage current < 1.0mA @ 264Vac
Extreme low temperature cold start at -40°C
NEC Class 2 / Limited Power Source (LPS) certified
Overvoltage / Overcurrent / Over Temperature Protections
Certified according to IEC/EN/UL 62368-1
Safety Standards
CB Certified for worldwide use
Model Number:
Unit Weight:
Dimensions (L x W x D):
Rated Output Voltage
24Vdc
1
Single Phase
DRS-24V30W1NZ
0.11 kg (0.24 lb)
75 x 21 x 89.5 mm
(2.95 x 0.83 x 3.52 inch)
Rated Output Current
1.25A
N
Z
NEC Class 2
Without DC OK
Relay Contact

Advertisement

Table of Contents
loading

Summary of Contents for Delta DRS-24V30W1NZ

  • Page 1 General Description The ultra-compact and competitively priced Delta Sync DIN rail power supply series is designed for industrial applications requiring highly reliable power supply within a tight space. The Sync series operates with universal AC input range and offers full power up to 55°C.
  • Page 2: Specifications

    TECHNICAL DATASHEET Sync DIN Rail Power Supply 24V 30W 1 Phase (NEC Class 2) / DRS-24V30W1NZ Specifications Input Ratings / Characteristics Nominal Input Voltage 100-240Vac Input Voltage Range 85-264Vac Nominal Input Frequency 50-60Hz Input Frequency Range 47-63Hz DC Input Voltage Range*...
  • Page 3 TECHNICAL DATASHEET Sync DIN Rail Power Supply 24V 30W 1 Phase (NEC Class 2) / DRS-24V30W1NZ Mechanical Case Cover / Chassis Plastic Dimensions (L x W x D) 75 x 21 x 89.5 mm (2.95 x 0.83 x 3.52 inch) Unit Weight 0.11 kg (0.24 lb)
  • Page 4 TECHNICAL DATASHEET Sync DIN Rail Power Supply 24V 30W 1 Phase (NEC Class 2) / DRS-24V30W1NZ Reliability Data MTBF Telcordia SR-332 > 700,000 hrs I/P: 115Vac & 230Vac, O/P: 100% load, Ta: 25°C MIL-HDBK-217F 260,000 hrs I/P: 115Vac & 230Vac, O/P: 100% load, Ta: 25°C...
  • Page 5 TECHNICAL DATASHEET Sync DIN Rail Power Supply 24V 30W 1 Phase (NEC Class 2) / DRS-24V30W1NZ Emissions (CE & RE) Generic Standards: EN 61000-6-3, EN 61000-6-4 CISPR 32, EN 55032 EN 55011, FCC Title 47: Class B Component Power Supply for General Use...
  • Page 6: Block Diagram

    TECHNICAL DATASHEET Sync DIN Rail Power Supply 24V 30W 1 Phase (NEC Class 2) / DRS-24V30W1NZ Block Diagram Device Description Input terminal block connector Output terminal block connector DC voltage adjustment potentiometer DC OK LED (Green) Universal mounting system All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
  • Page 7: Engineering Data

    TECHNICAL DATASHEET Sync DIN Rail Power Supply 24V 30W 1 Phase (NEC Class 2) / DRS-24V30W1NZ Dimensions L x W x D: 75 x 21 x 89.5 mm [2.95 x 0.83 x 3.52 inch] Engineering Data Output Load De-rating VS Surrounding Air Temperature...
  • Page 8: Assembly And Installation

    TECHNICAL DATASHEET Sync DIN Rail Power Supply 24V 30W 1 Phase (NEC Class 2) / DRS-24V30W1NZ Output Load De-rating VS Input Voltage No output power de-rating across the entire  input voltage range Assembly & Installation The power supply unit (PSU) can be mounted on 35mm DIN rails in accordance with EN60715. The device should be installed with input terminal block at the bottom.
  • Page 9 TECHNICAL DATASHEET Sync DIN Rail Power Supply 24V 30W 1 Phase (NEC Class 2) / DRS-24V30W1NZ Safety Instructions • ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the device. If mains are not turned OFF, there is risk of explosion / severe damage.
  • Page 10 TECHNICAL DATASHEET Sync DIN Rail Power Supply 24V 30W 1 Phase (NEC Class 2) / DRS-24V30W1NZ Functions Graph illustrating the Start-up Time, Rise Time, and Hold-up Time  Start-up Time The time required for the output voltage to reach 90% of its final steady state set value, after the input voltage is applied.
  • Page 11 TECHNICAL DATASHEET Sync DIN Rail Power Supply 24V 30W 1 Phase (NEC Class 2) / DRS-24V30W1NZ Overload & Overcurrent Protections (Auto-Recovery) Overvoltage Protection (Latch Mode) The power supply’s Overload (OLP) and Overcurrent (OCP) The power supply’s overvoltage circuit will be activated when its...
  • Page 12 TECHNICAL DATASHEET Sync DIN Rail Power Supply 24V 30W 1 Phase (NEC Class 2) / DRS-24V30W1NZ Operating Mode Redundant Operation  In order to ensure proper redundant operation for the power supply units (PSUs), the output voltage difference between the two units must be kept at 0.45~0.50V for these 24V supplies.
  • Page 13 Attention Delta provides all information in the datasheets on an “AS IS” basis and does not offer any kind of warranty through the information for using the product. In the event of any discrepancy between the information in the catalog and datasheets, the datasheets shall prevail (please refer to www.DeltaPSU.com for the latest datasheets information).

Table of Contents