TECHNICAL DATASHEET
CliQ DIN Rail Power Supply
24V 60W 1 Phase / DRP024V060W1AA
Safety Instructions
Vertical Mounting
•
ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the unit. If mains are not turned
OFF, there is risk of explosion / severe damage.
To guarantee sufficient convection cooling, please refer to the following instructions to ensure sufficient clearance around
•
the device.
Vertical Mounting: 50mm (1.97 inch) above and below the device as well as a lateral distance of 20mm (0.79 inch) to other
units.
Horizontal Mounting: 50mm (1.97 inch) above and below the device as well as a lateral distance of 50mm (1.97 inch) to
other units.
•
Note that the enclosure of the device can become very hot depending on the surrounding air temperature and load of the power
supply. Risk of burns!
•
Only plug in and unplug connectors when power is turned off!
DO NOT insert any objects into the unit.
•
•
Hazardous voltages may be present for up to 5 minutes after the input mains voltage is disconnected. Do not touch the unit during
this time.
•
The power supplies unit must be installed in an IP54 enclosure or cabinet in the final installation. The enclosure or cabinet must
comply with EN 60079-0 or EN 60079-15.
•
CAUTION: "For use in a controlled environment".
Warning: Explosion Hazard - Substitution of components may impair suitability for Class I, Division 2.
•
•
Warning: Explosion Hazard - Do not disconnect equipment unless the power has been switched off or the area is known to be non-
hazardous.
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
9
www.DeltaPSU.com (November 2020, Rev. 08)