Blink SemaConnect US User's Manual & Installation Instructions page 19

30kw wall mount dc fast charger
Table of Contents

Advertisement

Installing Cables
STEP 1.
Remove 2 of M5 screws and push the button (marked as no.3) to open front
cover :
STEP 2.
Please use XLPE power cables or equivalent for AC input connection, power
cable outer diameter is between 32 and 40mm. If XLPE cable is not available,
please use conduit hub and conduit size M50 to prevent electrical hazards
and do best water proof. the requirements of conduit shall be according to
EN61386-24 or followed local laws and regulations.
Each wire shall be crimped with the corresponding terminal before feeding. L1,
L2, L3 and N shall chose terminals with inner diameter 6.4mm and outer diam -
eter 16.5mm, PE shall chose terminals with inner diameter 5.3mm and outer
diameter 12mm. And then feeding the cable from bottom side and passing
through the cable gland.
3
1
2
OD
ID
Terminal
17
1
loosen
loosen
3
tighten
tighten
2
semaconnect.com