3.4 MACHINE WITH WATER-COOLED CONDENSER
Machines fitted with a water-cooled condenser need to be connected to running water supply or
to a cooling tower.
Water must have a pressure between 0.1 MPa/14 PSI and 0.5 MPa/72 PSI (1-5 bar) and a delivery
at least equal to the estimated hourly consumption.
Connect inlet pipe marked by plate "Water Inlet" to water supply installing a shut-off valve, and
outlet pipe marked by plate "Water Outlet" to a drain pipe, installing a shut-off valve.
Drinking water
inlet
Water inlet
Water outlet
Fig. 11

3.4.1 Water valve adjustment

IMPORTANT:
If water valve must be reset, this operation shall be carried out by skilled personnel, only.
Valve adjustment must be carried out in such a way that no water flows when machine is off and
lukewarm water flows when machine is on.
NOTE:
Water consumption increases if temperature of inlet water is above 68° F.
WARNING!
Do not leave the machine in a room with temperature below 32°F without
first draining water from the condenser (see Sec. 7 of the manual).