6 Set up with the display and adjustment module
Setup
Menu item
Measurement loop name
Application
Units
Position correction
Adjustment
Damping
Linearisation
Current output
Lock adjustment
Display
Menu item
Menu language
Displayed value 1
Displayed value 2
Display format
Backlight
44
Parameter
19 alphanumeric characters/special
characters
Level, process pressure
Secondary Device for electronic differen-
tial pressure
2)
Adjustment unit (m, bar, Pa, psi ... user-
defined)
Temperature unit (°C, °F)
Offset
Zero/Min. adjustment
Span/Max. adjustment
Integration time
Linear, cylindrical tank, ... user-defined
Current output - Mode
Output characteristics: 4 ... 20 mA,
20 ... 4 mA
Failure mode: ≤ 3.6 mA, ≥ 20 mA, last
measured value
Current output - Min./Max.
Min. current: 3.8 mA, 4 mA
Max. current: 20 mA, 20.5 mA
Blocked, released
Default value
Selected language
Pressure
Ceramic measuring cell: Measuring cell temperature in °C
Metallic measuring cell: Electronics temperature in °C
Number of positions after the decimal point, automatically
Switched on
Parameter only active if the instrument is connected to the Secondary Device
2)
Default value
Sensor
Level
Deactivated
mbar (with nominal measuring range
≤ 400 mbar)
bar (with nominal measuring ranges
≥ 1 bar)
°C
0.00 bar
0.00 bar
0.00 %
Nominal measuring range in bar
100.00 %
1 s
Linear
4 ... 20 mA
≤ 3.6 mA
3.8 mA
20.5 mA
Released
VEGABAR 87 • 4 ... 20 mA/HART