installation
HorizontalCo-LinearVentKit(MasonryFireplacesOnly)
APPLICATION
This instruction applies to the DuraVent DirectVent Pro termination system and is intended as a supplement to the applicable DirectVent Pro instructions.
This termination and venting system and the gas appliance were tested and listed by an accredited test agency.
Kit # 46DVA-HCL33 includes:
1 Horizontal Termination Cap
2 x 10' (3 m) long x 3" (76 mm) round liners and hardware.
The 948-128 Mil-Pac sealant must be purchased separately.
The intake and the exhaust are 3" (76 mm).
INSTALL INFORMATION
The flue damper must be fully blocked open or removed if safe to do so for installation of the unit. Ensure the fireplace and chimney are clean and in good
working order, and that all chimney cleanouts are tight-fitting and not permitting air into the chimney. Install a sealed vent cap and metal flashing at the
top of the masonry chimney to prevent leaks and air movement within the cavity.
This appliance is only certified for use with NG when terminating horizontally (LP is not permitted). Make the hole on the outer portion of the masonry
fireplace by boring it or removing bricks. Ensure that the masonry structure is safe and brick can be removed without damage to the chimney prior to
proceeding. Minimum and maximum vent heights are noted below.
For complete instructions follow this link:
https://duravent.com/wp-content/uploads/2020/06/L954-SUP_820018997-DirectVent-Pro-Horizontal-Vent-Kit_03-20-20_V1.pdf [duravent.com]
FPI is not responsible for the
integrity of the masonry fireplace
and or its repairs. Please consult
with your local authorities.
NG
NG Only
C
*Restrictor Set 4
4-1/2" Open
B
A
DIMENSIONS
A - Min. Height
B - Max. Height
C - Max. Horizontal
*See page 20 for instructions on setting the
restrictor.
24
| Gi29 Direct Vent Gas Insert
DIMENSIONS
MAX HEIGHT - A
MIN HEIGHT - B
MAX HORIZONTAL - C
9 ft. (2.7 m)
10 ft. (3 m)
18" (457 mm)
The exhaust is located on the left side and the
air intake on the right when facing the back of
the termination as shown below. Seal the 3" (76
mm) flex with Mil-Pac, purchased separately.
3 screws per each
end of length
Hose
Clamp
9' (2.7m)
10' (3m)
18" (45cm)
Installers must mechanically attach the supplied label
to the inside of the firebox of the fireplace into which
the gas fireplace insert is installed.
This fireplace has been converted for use with
a gas fireplace insert only. It cannot be used for
burning wood or solid fuels unless all original
parts are replaced and the fireplace re-approved
by the authority having jurisdiction.
Air
Intake
Exhaust