F043-T TEMPERATURE INDICATOR WITH HIGH / LOW TEMPERATURE ALARMS Signal input sensor: PT100 Alarm output: one temperature alarm. Options: Intrinsically Safe. F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries...
This unit must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility). Do connect a proper grounding to the aluminum casing as indicated if the F043-T has been supplied with the 115-230V AC power-supply type PM. The green / yellow wire between the back-casing and removable terminal-block may never be removed.
This operation manual describes the standard unit as well as most of the options available. For additional information, please contact your supplier. A hazardous situation may occur if the F043-T is not used for the purpose it was designed for or is used incorrectly. Please carefully note the information in this operating manual indicated by the pictograms: A "warning"...
Safety rules and precautionary measures ....................... 2 About the operation manual ..........................3 Contents manual .............................. 4 Introduction ..........................5 1.1. System description of the F043-T ..................5 Operational ..........................6 2.1. General ..........................6 2.2. Control panel .......................... 6 2.3.
Fig. 1: Typical application for the F043-T. Configuration of the unit The F043-T has been designed to be implemented in many types of applications. For that reason, a SETUP-level is available to configure your F043-T according to your specific requirements.
Take careful notice of the " Safety rules, instructions and precautionary measures " in the front of this manual. This chapter describes the daily use of the F043-T. This instruction is meant for users / operators. 2.2. CONTROL PANEL The following keys are available: Fig.
SETUP-settings. The signal generated by the connected sensor is measured by the F043-T in the background, whichever screen refresh rate setting is chosen. After pressing a key, the display will be updated very quickly during a 30 second period, after which it will slow-down again.
Page 8
Page 8 Temperature alarm When the actual temperature is outside the allowed range, an alarm message will be displayed indicating the type of alarm: "LO TEMP", "HI TEMP". The alarm is terminated automatically as soon as the temperature is within its range again. ...
Operating Manual before carrying out its instructions. The F043-T may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
Page 10
Page 10 Matrix structure SETUP-level: SCROLLING THROUGH SETUP-LEVEL Selection of function-group and function: SETUP is divided into several function groups and functions. Each function has a unique number, which is displayed below the word "SETUP" at the bottom of the display. The number is a combination of two figures. The first figure indicates the function-group and the second figure the sub-function.
Page 11
Page 11 To change or select a value: To change a value, use to select the digits and to increase that value. If the new value is invalid, the increase sign or decrease-sign will be displayed while you are programming.
When used with the internal battery option, the user can expect reliable measurement over a long period of time. The F043-T has several smart power management functions to extend the battery life time significantly. Two of these functions can be set:...
The output signal of a sensor does mirror the actual temperature. This FILTER signal is measured several times a second by the F043-T. The value measured is a "snap-shot" of the real temperature as it will be fluctuating. With the help of this digital filter a stable and accurate reading can be obtained while the filter temperature can be set to a desired value.
Operating Manual before carrying out its instructions. The F043-T may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
Page 18 4.4. INSTALLING THE HARDWARE 4.4.1. INTRODUCTION Electro static discharge does inflict irreparable damage to electronics! Before installing or opening the unit, the installer has to discharge himself by touching a well-grounded object. This unit must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility).
PT100 - 2 WIRE PT100 - 3 WIRE PT100 - 4 WIRE Fig. 9: Overview of terminal connectors F043-T-(PB / PX) and options. REMARKS: TERMINAL CONNECTORS: Terminals 1-4; Sensor input type T – PT100: See drawing above for the proper connection of a 2, 3 or 4 wire PT100 sensor. The sensor signal which will be processed once per second with a 16 bits accuracy.
Safety Instructions Certificates, safety values, control drawing and declaration of compliance can be found in the document named: “Fluidwell F0..-T-XI - Documentation for Intrinsic Safety”. For installation under ATEX directive: this intrinsically safe device must be installed in accordance with the Atex directive 94/9/EC and the product certificate KEMA 05ATEX1168 X.
FWCD-0005. Tamb CSA Certificate nr: CSA.08.2059461 – FM Project ID: 3033306 -40°C ... +70°C Made in Veghel, The Netherlands by Fluidwell bv -40°F ... +158°F KEMA 05ATEX1168 X Battery powered applications: II 1 G Ex ia IIC T4 Replace with certified II 1 D Ex iaD 20 IP 65 / 67 T 100°C...
Type PX: as standard, all intrinsically safe products are supplied with terminal 4 and 5 to power the product externally. 5.3. CONFIGURATION EXAMPLES INTRINSICALLY SAFE APPLICATIONS: Configuration example Configuration example IIA - IIB and IIC application - F043-T-PX-XI-ZB HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F0-series = max.
Operating Manual before carrying out its instructions. The F043-T may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
Page 25 APPENDIX A: TECHNICAL SPECIFICATION GENERAL Display Type High intensity reflective numeric and alphanumeric LCD, UV-resistant. Digits Seven 17mm (0.67") and eleven 8mm (0.31"). Various symbols and measuring units. Refresh rate User definable: 8 times/sec - 30 secs. Type ZB (option) Tri-color configurable LED-backlight - green, amber with red flashing during alarm.
Page 26
Page 26 Data protection Type EEPROM backup of all settings. Data retention at least 10 years. Pass code Configuration settings can be pass code protected. Hazardous area (option) Intrinsically safe ATEX approval: Type XI II 1 G Ex ia IIC T4 II 1 D Ex iaD 20 IP 65 / 67 T 100°C IECEx approval: Ga Ex ia IIC T4...
Page 27 APPENDIX B: PROBLEM SOLVING In this appendix, several problems are included that can occur when the F043-T is going to be installed or while it is in operation. Range error Range error: the input value is at least 5% above or below the calibrated measurement range.
Page 28 INDEX OF THIS MANUAL actual settings low current alarm 8, 27 low-battery alarm output function main-function alarm values maintenance delay time alarm manual version set alarm operator level model alarm output operational alarm values operator level backlight pass code 14, 27 alarm color power supply...