Do not place anything on top of the universal gateway that weighs more than 10 lb (4.5 kg). Excessive weight on
Caution
top could damage the chassis.

Chassis Ground Connection

You must connect the chassis to a reliable earth ground by using the ground lug (provided) and size AWG 6 (13 mm
To attach the chassis ground, follow these steps:
Strip one end of the ground wire to expose approximately 0.75 in. (20 mm) of conductor.
Step 1
Step 2
Crimp the ground wire to the ground lug, using a crimp tool of the appropriate size.
Step 3
Attach the ground lug to the chassis as shown in Figure 7 and Figure 8. Use a medium flat-blade screwdriver and the
screws supplied with the ground lug. Tighten the screws to a torque of 8 to 10 in-lb (0.9 to 1.1 N-m).
Figure 7
Cisco AS5350XM Universal Gateway Ground Lug Attachment
Ground lug
attachment
Figure 8
Cisco AS5400XM Universal Gateway Ground Lug Attachment
Connect the other end of the ground wire to a suitable grounding point at your site.
Step 4
8
Ground lug
attachment
2
) wire.