Connect Dc Power - Cisco AS5400XM Quick Start Manual

Universal gateways
Table of Contents

Advertisement

Figure 37
Connecting the AC Power Cables to the Cisco AS5400XM Universal Gateway
Connect the other end of the power cable to the electrical outlet.
Step 2
If your universal gateway has a redundant power supply installed, repeat Step 1 and Step 2 for the second power supply.
Step 3

Connect DC Power

Warning
A readily accessible two-poled disconnect device must be incorporated in the fixed wiring. Statement 1022
Warning
This product relies on the building's installation for short-circuit (overcurrent) protection. Ensure that a UL Listed
and Certified fuse or circuit breaker no larger than 60 VDC, 15 A is used on all current-carrying conductors.
Statement 96
If you ordered the universal gateway with a DC-input power supply, follow the directions in this section for proper wiring.
In a DC power supply installation, do not connect the 48 VDC Return wire to chassis ground at the universal
Caution
gateway. A single-point ground is recommended at the power distribution rack.
Note
This product is intended for installation in restricted access areas and is approved for connection using number 12 or
number 14 AWG copper conductors only. The installation must comply with all applicable codes.
To connect DC power, follow these steps:
Remove power from the DC circuit.
Step 1
Warning
Before connecting or disconnecting ground or power wires to the chassis, ensure that power is removed from the
DC circuit. To ensure that all power is OFF, locate the circuit breaker on the panel board that services the DC
circuit, switch the circuit breaker to the OFF position, and tape the switch handle of the circuit breaker in the OFF
position. Statement 140