Download Print this page

Beretta Ciao X Series Installer And User Manual page 25

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 20
b
As envisaged by current legislation, the boiler is designed to take
in and dispose of flue gas condensate and/or meteoric water con-
densate deriving from the flue gas discharge system using its own
b
siphon.
If a condensate relaunch pump is installed, check the technical
data (provided by the manufacturer) regarding output, to ensure
it operates correctly.
- Position the discharge pipe so that the connection sits fully up against
the flue gases turret of the boiler.
- After positioning it, make sure the 4 notches (A) slip into the groove
(B).
- Fully tighten the screws (C) that hold the two flange locking terminals,
so the bend itself is restrained held in place.
B23P-B53P Ø60-100
Ø80-80
B
B
A
C
b
If the Ø 60-100 to Ø 80-80 splitter kit is used instead of the twin
pipe system, there is a loss in the maximum lengths as shown in
the table.
Loss of length (m)
Twin pipes with Ø 80 pipework (Ø50 - Ø60 - Ø80)
Thanks to the boiler characteristics, a Ø80 flue gas exhaust pipe can be
connected to the Ø50 - Ø60 - Ø80 piping ranges.
b
For the pipe, you are advised to make a project calculation in order
to respect the relevant regulations in force.
The table shows the standard configurations allowed.
Air suction
Flue gas
Reduction from Ø80 to Ø50 from Ø80 to Ø60
discharge
Flue base bend 90°, Ø50 or Ø60 or Ø80
For ducting pipe lengths see table
The boilers are factory set to:
CH rpm
7.000
7.000
7.400
Should greater lengths be required, compensate the pressure drop with
an increase in the r.p.m.of the fan, as shown in the adjustments table,
to provide the rated heat input, referring to paragraph "4.9 Adjustments".
b
The minimum calibration should not be modified.
b
In case of new fan speed adjustment, carry out the CO
procedure as indicated in paragraph "4.8 Combustion analysis".
Ø80-125
B
A
B
Ø 50
Ø 60
Ø 80
5,5 for flue gases pipe
0,5
1,2
7,5 for air pipe
1 bend 90° Ø 80
4.5m pipe Ø80
1 bend 90° Ø 80
4.5m pipe Ø80
DHW rpm
max length pipes (m)
Ø50
Ø60
6
19
8.700
1
9
8.700
4
16
8.700
0
7
Adjustment tables INSIDE CHIMNEY PIPES
Fan rotations rpm
CH
DHW
7.000
8.700
7.100
8.800
7.200
8.900
7.300
9.000
7.400
9.100
7.500
9.200
7.600
9.300
7.700
9.400
7.000
8.700
7.100
8.800
7.200
8.900
7.300
9.000
7.400
9.100
7.500
9.200
7.600
9.300
7.700
9.400
(*) Maximum length that can be installed ONLY with class H1 discharge pipes.
B
Fan rotations rpm
CH
DHW
7.000
8.700
7.100
8.800
7.200
8.900
7.300
9.000
C
7.400
9.100
7.500
9.200
7.600
9.300
7.700
9.400
7.400
8.700
7.500
8.800
7.600
8.900
7.700
9.000
7.800
9.100
7.900
9.200
8.000
9.300
8.100
9.400
(*)
Maximum length that can be installed ONLY with class H1 discharge pipes.
The Ø50 or Ø60 or Ø80 configurations contain Lab test data. In the event
of installations that differ from the indications in the "standard configu-
rations" and "adjustments" tables, refer to the equivalent linear lengths
below.
b
In any case, the maximum lengths declared in the booklet are gua-
ranteed, and it is essential not to exceed them.
COMPONENT
Bend 45°
Bend 90°
Extension 0.5m
Extension 1.0m
Extension 2.0m
Installation on collective flues in positive
3.9
pressure
The collective flue is a flue gas exhaust system suitable for collecting
and expelling the combustion products of several appliances installed on
several floors of a building.
The positive pressure collective flues can only be used for type C con-
densing appliances. Therefore the B53P/B23P configuration is forbid-
den. The installation of boilers under collective pressure flues is allowed
Ø80
exclusively in G20.
The boiler is sized to operate correctly up to a maximum internal pressure
95
of the flue no higher than the value of 25 Pa. Check that the fan speed
corresponds to what is shown in the "technical data" table.
Make sure that the air intake and exhaust pipes of the combustion prod-
45
ucts are watertight.
80
WARNIGS:
b
The appliances connected to a collective pipe must all be of the same
35
b
type and have equivalent combustion characteristics.
The number of devices connected to a positive pressure collective
pipe is defined by the flue designer.
The boiler is designed to be connected to a collective flue sized to op-
erate in conditions where the static pressure of the collective flue pipe
can exceed the static pressure of the collective air duct of 25 Pa in the
condition in which n-1 boilers work at maximum rated heat input and 1
boiler at the minimum rated heat input allowed by the controls.
check
2
25
twin flue pipe
Pipes Ø50
Pipes Ø60
Pipes Ø80
Maximum length (m)
6
19
95
12 *
33 *
165 *
16 *
39 *
195 *
19 *
46 *
230 *
23 *
53 *
265 *
27 *
61 *
305 *
29 *
67 *
335 *
32 *
73 *
365 *
4
16
80
8 *
26 *
130 *
11 *
32 *
160 *
14 *
38 *
190 *
17 *
44 *
220 *
19 *
50 *
250 *
22 *
56 *
280 *
25 *
62 *
310 *
compact twin flue pipe
Pipes Ø50
Pipes Ø60
Pipes Ø80
Maximum length (m)
1
9
45
7 *
23 *
115 *
11 *
29 *
145 *
14 *
36 *
180 *
18 *
43 *
215 *
22 *
51 *
255 *
24 *
57 *
285 *
27 *
63 *
315 *
0
7
35
4 *
17*
85 *
7 *
23 *
115 *
10 *
29 *
145 *
13 *
35 *
175 *
15 *
41 *
205 *
18 *
47 *
235 *
21 *
53 *
265 *
Linear equivalent in metres Ø80 (m)
Ø 50
12,3
19,6
6,1
13,5
29,5
EN
∆P at boiler outlet
180
260
300
342
383
431
465
500
180
260
300
342
383
431
465
500
∆P at boiler outlet
180
260
300
342
383
431
465
500
190
256
300
340
380
417
458
500
Ø 60
5
8
2,5
5,5
12

Advertisement

loading