Soft start/quick exhaust valve
Table of Contents

Advertisement

Technical data
EN2 before EN1 (for multi-pin plug socket NECA-S1G9-P9-MP1)
1
2
3
Fig. 21: Runtime performance of enable signals with NECA-...-MP1
1 EN2: Enable signal 2
2 EN1: Enable signal 1
Maximum reaction time from exhausting to pressurisation: t2 + t1 = 75 ms + 5 ms = 80 ms
Maximum reaction time from pressurisation to exhausting: t3 + t4 = 15 ms + 2 ms = 17 ms
EN1 before EN2 (for multi-pin plug socket NECA-S1G9-P9-MP1)
1
2
3
Fig. 22: Runtime performance of enable signals with NECA-...-MP1
1 EN2: Enable signal 2
2 EN1: Enable signal 1
Maximum reaction time from exhausting to pressurisation: t2 + t1 + t4 = 75 ms + 5 ms + 2 ms = 82 ms
Maximum reaction time from pressurisation to exhausting:
t2 + t3 + t4 = 75 ms + 15 ms + 2 ms = 92 ms
32
3 Signal contacts
3 Signal contacts
Festo — MS6(N)-SV-...-E-10V24 — 2021-11e