Servomotor (Sqm10 - Riello DB 6 LSM C13 Installation, Use And Maintenance Instructions

Dual fuel light oil/gas burner type 14304y
Table of Contents

Advertisement

Available languages

Available languages

3.14 Servomotor (SQM10...)

Warnings
To avoid accidents, material or environmental
damage, observe the following instructions!
Avoid opening, modifying or forcing the actua-
WARNING
tors.
 All interventions (assembly and installation operations,
assistance, etc.) must be carried out by qualified personnel.
 Before modifying the wiring in the connection area of the
servomotor, fully disconnect the burner control device from
the power supply (omnipolar separation).
 To avoid the risk of electrocution, protect the connection ter-
minals in a suitable manner and correctly fix the cover.
 Check the wiring is in order.
 Falls and collisions can negatively affect the safety func-
tions. In this case, the servomotor must not be operated,
even if it displays no evident damage.
Assembly notes
Check the relevant national safety standards are respected.
When assembling the servomotor and connecting the damp-
er, the gears can be disengaged by means of a lever, allow-
ing the drive shaft to be easily adjusted in both directions of
rotation.
20114504
Technical description of the burner
Technical data
13
GB
S8413
Operating voltage
AC 220...240V, 50 Hz –15 % / +10 %
AC 220 V, 60 Hz –15 % / +10 %
Auxiliary and limit switch-
10 (3) A, AC 24...250 V
es switching capacity
Angular positioning
up to 160 ° (base scale)
Assembly position
optional
Protection level
IP 54, DIN 40050
Safety class
GB
Weight
approx. 1.7 kg
Actuator motor
synchronous motor
Power absorption
9 VA
Environmental conditions:
Operation
DIN EN 60 721-3-1
Climatic conditions
Class 1K3
Mechanical conditions
Class 1M2
Temperature range
-20...+70°C
Humidity
< 95% RH
Fig. 9
Tab. F

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

20114304