To calibrate the flow rate range within which the nozzle should
operate, it is necessary to adjust the fuel pressure on the nozzle
return line, according to (Tab. H, Tab. I).
 Do not use any sealing products such as gas-
kets, sealing compound, or tape.
 Be careful to avoid damaging the nozzle seal-
WARNING
ing seat.
 The nozzle must be screwed into place tightly
but not to the maximum torque value pro-
vided by the wrench.
4.10.1 Recommended nozzles
Bergonzo type B5 45°
Fluidics type N4 45°
For intermediate delivery levels, choose the nozzle with delivery
slightly higher than that effectively required.
Complete range of nozzles:
 Bergonzo type B5 45° 350 - 375 - 400 - 425 - 450 - 475 -
500 - 525 - 550 - 575 - 600 - 650 - 700 - 750. Normally, ato-
misation angles of 45° are recommended.
Delivery
kg/h
pressure
bar
20
375
20
20
550
20
20
650
20
25
750
25
 Fluidics type N4 45°: 375 - 400 - 450 - 500 - 550 - 600 - 650
- 700 - 750. Normally, atomisation angles of 45° are recom-
mended.
Delivery
kg/h
pressure
bar
20
375
20
20
550
20
20
650
20
25
750
25
20114504
Return
pressure
kg/h
bar
11.5
147
1750
17
295
3500
10
170
2000
17
421
5000
8
180
2150
16.5
565
6650
11.5
227
2700
20.5
675
8000
Return
pressure
kg/h
bar
12
147
1750
18.5
295
3500
7
170
2000
16
421
5000
6
180
2150
17
565
6650
17
227
2700
22
675
8000
Installation
kW
Example:
Nominal nozzle output:
Tab. H
Maximum output requested:
Pressure on return line:
Required modulating ratio:
Minimum output:
Pressure on return line:
kW
Outlet pressure:
Oil viscosity:
Tab. I
19
GB
S9696
Delivery (%)
800 kg/h
760 kg/h (95%)
20 bar
1:3,8
200 kg/h (25%)
7 bar
25 bar
2 °E
Fig. 19
D8033
Fig. 20

Advertisement