Emerson Rosemount ET310 Quick Start Manual page 28

Wireless permasense corrosion transmitter
Hide thumbs Also See for Rosemount ET310:

Advertisement

Quick Start Guide
Figure 4-4: Commissioning Kit
2. Double-click the Permasense installation application desktop icon.
Within approximately 10 seconds, the Permasense installation tool
software should open.
3. Attach the CC21 to the sensor.
4. In the installation application software:
Note
Joining the device to the network could take several minutes.
28
A. Tablet PC
B. CC21 interface
C. USB cable
D. Rosemount Wireless Permasense Sensor
a) Verify both the sensor ID and the sensor's MAC address, which
are displayed at the top of the screen within 10 seconds.
b) Select the Provision tab.
c) Enter the 5-digit network ID and the 32-hexadecimal
(numbers 0-9 and letters A -F) join key.
d) Click the Provision button.
The system provides confirmation once provisioning is
complete.
e) Ensure the network ID of the gateway is visible in the Network
Discovery panel.
January 2022
Emerson.com/Rosemount