Power Supply Connection - FAAC E012 Instruction Manual

Table of Contents

Advertisement

Rev. 01.2006 - Istallation Manual
Page 7
Terminals "14-18" (OPEN A-COM1): Normally open contact. Connect, to these terminals, any pulse generator
(e.g. push-button, key selector, etc..) which, by closing a contact, generates a pulse for totally opening or
closing the gate. The operation of this input is defined by dip-switch 3 - see paragraph 2.5.1.
Terminals "15-18" (OPEN B-COM1): Normally open contact. Connect, to these terminals, any pulse generator
(e.g. push-button, key selector, etc..) which, by closing a contact, generates a pulse for partially opening
the gate.
In two-motor installations (Dip-switch 5=ON); partial opening corresponds to the total opening of the leaf
on which the motor M1 is installed.
In single-motor applications (Dip-switch 5=OFF), partial opening coincides with an opening of about ~80%
of the total memory-stored opening.
If a total opening command (OPEN A) is given during the partial opening stage, the control unit memory
stores the command, which is executed when partial opening has finished.
Terminals "16-18" (FSW-COM1): Normally closed contact. Connect, to these terminals, any safety device
(photocell, pressure switch, safety edge etc..) which, by opening a contact, affects the gate's closing
motion, reversing it to the mechanical opening stop, without disabling automatic re-closure if it is enabled.
The status of this input is signalled by LED "FSW".
This contact can be disabled with dip-switch 6 - see paragraph 2.5.1.
If you decide to disable the photocells, you do not have to jumper the input.
The control unit is supplied with the photocell input disabled.
Terminals "17-18" (STOP-COM1): Normally closed contact. Connect, to these terminals, any pulse generator
(push-button, key selector, etc..) which, by opening a contact, immediately stops the gate and disables all
automatic functions. The status of this input is signalled by the "STOP"LED. The gate resumes its memory-
stored cycle only by means of another total or partial opening pulse.
This contact can be disabled with dip-switch 7 - see paragraph 2.5.1.
If you decide to disable the stop command, you do not have to jumper the input.
The control unit is supplied with the stop command input disabled.
TERMINAL BOARD CN4
5-terminal connector for coupling receiver.
DIP-SWITCH
DP1(SW1): Parameter adjustment, see paragraph 2.5.1.
F U S E S
F1: 16A T 250V 5X20.
F2: 10A T 250V 5X20.
L E D S
POWER:
Control unit fed by transformer
F SW:
Safety device disengaged or input disabled.
STOP:
Command inactive or input disabled.
Indicated in bold: status of LEDs with the gate closed, and control unit fed by transformer.

2.2.3 POWER SUPPLY CONNECTION

As concerns power supply:
1 Use a 3 x 15 mm2 cable for conveying the 230V mains current, protected by a fuse or by a 10 Amp
circuit breaker, routing from the dwelling to the gate.
ON
OFF
No power supplied, or control unit fed by
batteries.
Safety device engaged, contact open.
Command active, contact open.