Master Programming Level
Report Style
The DACT can be programmed to transmit reports to primary and/or secondary central station phone numbers as a backup. Press 2 while
viewing Central Station Screen #1 to display the following screen:
Press 1 to have all reports transmitted to the central station secondary phone number as a backup only if the primary phone line fails, 2 to
transmit all reports to both the primary and secondary phone numbers all of the time, or 3 to send reports to the first available phone
number.
GF505 & GF510 Manual — P/N 53164:B5 6/12/2018
REPORT STYLE
1=BACKUP ONLY
2=BOTH
3=FIRST AVAILABLE
Backup Reporting Screen
Programming
67