Ann-Bus - Honeywell GF505 Manual

Fire alarm control panels
Table of Contents

Advertisement

Master Programming Level
Pressing 2 while viewing Programming Screen #2 will display the following screen:

ANN-BUS

Pressing 1 while viewing the Option Modules screen will cause the control panel to display the following screens.
1=BUS ENABLED
2=BUS MODULES
3=AUTO CONFIGURE
A variety of ANN-BUS option modules can be installed in the FACP. These devices communicate with the FACP over the ANN-BUS
terminals on the control panel.
ANN-BUS Enabled
The ANN-BUS must be enabled if any modules are installed on the ANN-BUS terminals. To enable the ANN-BUS, press 1 while view-
ing ANN-BUS screen #1 so that the display reads ANN-BUS Enabled Yes. Each press of the 1 key will cause the display to toggle
between ANN-BUS Enabled Yes and ANN-BUS Enabled No.
BUS Modules
If an ANN-BUS module is installed, press 2 while viewing ANN-BUS screen #1 to select ANN-BUS addresses for the module(s). The
following screen will be displayed.
Pressing the down arrow key will allow the programmer to view additional screens displaying Addresses 1 - 8. Pressing the number cor-
responding to the desired address will display a screen with technical information about the selected module.
In the technical information screen, pressing 1 for Type will display the following screens:
ANN-BUS MODULE TYPE
1=NOT INSTALLED
2=ANN-80
3=ANN-I/O
Press the number corresponding to the module type, if any, that is installed with the selected address. This will enable the module.
Note that the ANN-I/O and ANN-S-P/G Module options are not presently available.
Auto-Configure
The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed ANN-BUS modules online. The software
will search for all ANN-BUS modules and automatically program the device type and address into the system. Pressing 3 while viewing
ANN-BUS Screen #1 will begin the Auto-Configure process and cause the following screen to be displayed:
ANN-80 Options Screen
Pressing 2 while viewing ANN-BUS screen #2 will display the following screen:
GF505 & GF510 Manual — P/N 53164:B5 6/12/2018
OPTION MODULES
1=ANN-BUS
2=ON BOARD DACT
ANN-BUS
NO
ANN-BUS Screen #1
1=ADDR. 1
2=ADDR. 2
3=ADDR. 3
Module Type Screen #1
ANN-80 OPTIONS
1=PIEZO ENABLE
2=LOCK ENABLE
3=ACK BTN ENABLE
ANN-80 Options Screen #1
ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-80 OPTIONS
3=ANN-RLY OPTIONS
ANN-BUS Screen #2
ANN-BUS MODULES
NONE
NONE
NONE
On Board DACT Screen #1
ANN-BUS MODULE TYPE
1=ANN-S/PG
2=ANN-RLY
3=ANN-LED
Module Type Screen #2
ANN-BUS
AUTO-CONGFIGURE
IN PROGRESS
PLEASE WAIT
Auto-Configure Screen
ANN-80 OPTIONS
1=SIL BTN ENABLE
2=RST BTN ENABLE
3=DRL BTN ENABLE
ANN-80 Options Screen #2
ANN-BUS
1=ANN-AUDIO OPTIONS
2=ANN-SEC ENABLE
NO
ANN-BUS Screen #3
ANN-BUS MODULE TYPE
1=ANN-AUDIO MODULE
Module Type Screen #3
Programming
63