Programming
Exit Programming and Read Status Mode
The programmer can exit any mode by repeatedly pressing the keypad ESC (Escape) key until the display reads System All Normal. Ten
minutes of inactivity will also cause the panel to exit Programming Mode Note that the data which is entered during Programming
mode is not saved until the programmer exits this mode by repeatedly pressing the 'ESC' key. If the Reset key is pressed or power is lost
before exiting Programming mode, all data just entered will be lost.
44
GF505 & GF510 Manual — P/N 53164:B5 6/12/2018
User Programming