Honeywell GF505 Manual page 51

Fire alarm control panels
Table of Contents

Advertisement

Master Programming Level
Pre-signal
The Pre-signal option programs the zone to delay panel activation for a preprogrammed time delay of up to three minutes while allowing
for visual verification by a person. Note that the alarm relay and communicator will respond to the initial alarm immediately. To enable
the Pre-signal feature, press 2 while viewing PAS/Pre-Signal Screen. Refer to "Presignal" on page 90.
GF505 & GF510 Manual — P/N 53164:B5 6/12/2018
Programming
51