M0087475-06
Illustration 55
Reduced Time
If the ECM is configured to "Reduced Time" and the
DEF level is 0%, the engine will be in level 3
inducement. The check engine lamp and emissions
malfunction indicator lamp will illuminate and flash at
a fast rate. A red stop lamp will illuminate solid. The
DEF level gauge amber lamp will remain lit. The
engine will have a 100% derate and be limited to
1000 rpm or low idle, whichever is greater. If the final
inducement action in the electronic service tool is set
to "Idle Down" , then the engine will continue to idle at
derated condition. If set to "Shutdown" , engine will
shut down after 5 minutes. Safe Harbor Mode is
allowed for three key cycles. After Safe Harbor Mode
is completed, the engine will return to idle or shut
down. If in shutdown configuration, the engine may
be restarted, but will only run for 5 minutes at derated
condition before shutting down again. This action will
continue until the issue is resolved.
Note: Turn the key to the OFF and add DEF to the
DEF tank to reset the DEF level inducement.
Inducement Strategy for Escalating
Time Inducement Faults (European
Union and China)
Illustration 56
Reduced Performance
Selective Catalytic Reduction Warning System
The check engine and emissions malfunction
indicator lamp will illuminate for any inducement-
related fault. There are two inducement categories. If
the inducement is a result of a category 1 fault, then a
level 1 inducement will occur for a duration of 36
hours. If the inducement is a result of a category 2
fault, then a level 1 inducement will occur for a
duration of 10 hours. There is no repeat occurrence
for level 1 faults.
Reduced Time
The check engine and emissions malfunction
indicator lamp will illuminate for a level 1 inducement-
related fault. There are two inducement categories. If
the inducement is a result of a category 1 fault, then a
level 1 inducement will occur for a duration of 18
g06751922
hours. If the inducement is a result of a category 2
fault, then a level 1 inducement will occur for a
duration of 5 hours. There is no repeat occurrence for
level 1 faults.
Illustration 57
Reduced Performance
If a fault condition exists for the entire duration of
inducement level 1, the strategy advances to
inducement level 2. The check engine lamp and the
emissions malfunction indicator lamp will illuminate
and flash slowly. If the inducement is a result of a
category 1 fault, then a level 2 inducement will occur.
The level 2 inducement occurs for a duration of 64
hours for first occurrence. For repeat occurrence, a
category 1 level 2 inducement fault will occur for a
duration of 5 hours.
If the inducement is a result of a category 2 fault, then
a level 2 inducement will occur for a duration of 10
hours. For repeat occurrence, a category 2 level 2
inducement fault will occur for a duration of 2 hours.
The engine will have a 50% derate. If the fault is not
corrected before the inducement duration ends, the
engine will become 100% derated. The engine will
also be limited to 1000 rpm or low idle, whichever is
greater. No further inducements will occur for
"Reduced Performance" configuration. Safe Harbor
Mode is allowed for three key cycles.
Reduced Time
g03677836
49