Forced Ventilation (by Fan at Top of Panel)
Fan
Air filter
Forced Ventilation Method
Forced Air Circulation (by Fan in Closed Panel)
Fan
Controller
Controller
Forced Air Circulation
Room Cooling (Cooling the Entire Room Where the Control Panel Is Located)
Low Temperatures
The Controller may not start normally if the temperature is below 0°C when the power is turned ON.
Maintain an air temperature of at least approximately 5°C inside the panel, by implementing measures
such as installing a low-capacity space heater in the panel.
Alternatively, leave the Controller power ON to keep the Controller warm.
NX-series CPU Unit Hardware User's Manual (W535)
Controller
Controller
Cooler
Control panel
Room Cooling
4 Installation and Wiring