A-1 Specifications

This section gives the specifications of the NX-series CPU Units.
Enclosure
Grounding method
Dimensions (height × depth × width)
Weight
Current consumption
Ambient operating tempera-
ture
Ambient operating humidity
Atmosphere
Ambient storage tempera-
ture
Altitude
Pollution degree
Noise immunity
Operating
Overvoltage category
environment
EMC immunity level
Vibration resistance
Shock resistance
Life
Battery
Model
EU Directives
Applicable
cULus
*1
Shipbuilding Standards
standards
Other than the above.
*1. Refer to the OMRON website (http://www.ia.omron.com/) or consult your OMRON representative for the most
recent applicable standards for each model.
A - 2
Item
Mounted in a panel
Ground to less than 100 Ω.
100 mm × 100 mm × 132 mm
880 g (including the End Cover)
40 W (including SD Memory Card and End Cover)
0 to 55°C
10% to 95% (with no condensation)
Must be free from corrosive gases.
-25 to 70°C (excluding battery and Fan Unit)
2,000 m max.
2 or less: Meets IEC 61010-2-201.
2 kV on power supply line (Conforms to IEC 61000-4-4.)
Category II: Meets IEC 61010-2-201.
Zone B
Conforms to IEC 60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz, acceleration
of 9.8 m/s
100 min each in X, Y, and Z directions (10 sweeps of 10 min
each = 100 min total)
Conforms to IEC 60068-2-27.
147 m/s
2.5 years (at 25°C, Power ON time rate 0% (power OFF))
CJ1W-BAT01
EN61131-2
Listed UL508 and ANSI/ISA 12.12.01
NK, LR
KC
NX7-
2
2
, 3 times in X, Y, and Z directions
NX-series CPU Unit Hardware User's Manual (W535)