Produal TRC-P Series Manual page 31

Touchscreen room controllers
Table of Contents

Advertisement

40129
40130
40131
40132
40133
40143
40144
40145
40146
40148
40149
40150
40151
40152
40153
40154
Property Name /ID
Required
Object Identifier
Object
Object Name
Properties
Object Type
Web-site: www.produal.com
Enquiries: T: +358 10 219 9100 E: info@produal.fi
Fan Speed Source
Min Fan Level
Y1 Output Mode
Default: Modulating Fan
Y2 Output Mode
Default: Heating Stage 1
Default TRC-1A4R: Heating1 Stat
Y3 Output Mode
Default: Cooling Stage 1
Anti-JAM Time-out
RI1 Mode
RI2 Mode
Outside Temperature Source
Digital Input Mode
Digital Input Delay
Internal Sensor Calibration
RI1 Calibration
RI2 Calibration
CO2 Calibration
Humidity Calibration
Attributes
R
R/W
R
Unsigned
0 = Heating 1 and Cooling 1 Stage (Default)
1 = Heating Stage1
2 = Cooling Stage 1
3 = Heating and Cooling Stage 2
4 = Heating Stage 2
5 = Cooling Stage 2
6 = CO2
7 = Humidification
8 = De-Humidification
9 = Maximum VAV (Cooling/CO2)
10 = Maximum Temp/Hum
11 = Aux. Loop
Unsigned
0...100% (Default 0%)
Unsigned
0 = Network Value
1 = Heating Stage 1
2 = Heating Stage 2
Unsigned
3 = Cooling Stage 1
4 = Cooling Stage 2
5 = Modulating Fan (EC)
Unsigned
6 = CO2 Control
7 = Maximum VAV
8 = Maximum Fan
9 = Humidification
10 = De-humidification
11 = Amber / Red
12 = Red
13 = Heating1 Stat
14 = Cooling1 Stat
15 = Fan Stat
16 = Aux. Loop
17 = 6-Port (Valve)
18 = 6-Port Reverse (Valve)
Unsigned
0..14 Days
0 = Disabled (Default)
Unsigned
0 = Disabled (default)
1 = Room (NTC10 Control)
Unsigned
2 = Floor (NTC10 High/Low Lim)
3 = Aux. Loop
4 = Network NTC10
5 = Network 0-10V
6 = CO2 0-10V (0..2000 =0-10V)
7 = Main Loop (0..50°C=0-10V)
8 = Close for ECO (DI-mode)
9 = Open for ECO (DI-mode)
10 = Close for OFF (DI-mode)
11 = Open for OFF (DI-mode)
Unsigned
0 = Built-In Sensor (Default)
1 = Network Sensor
Unsigned
0 = Close for ECO (Default)
1 = Open for ECO
2 = Close for OFF
3 = Open for OFF
4 = Heating/Cooling Change-Over
5 = Disable Cooling
6 = Contact Alarm
7 = Network Measurement
8 = Close for BOOST (CE only)
9 = Open for BOOST (CE only)
Unsigned
0..28,800 seconds (Default 0s)
REAL
-10.0..+10.0 °C/°F
REAL
-10.0..+10.0 °C/°F
REAL
-10.0..+10.0 °C/°F
REAL
-500...+500 ppm
REAL
-10.0..+10.0 % rH
Range
Default
proprietary-128
"Config2"
proprietary-128
Copyright © 2020 Produal Oy - All rights reserved - 07/2020