Produal TRC-P Series Manual page 22

Touchscreen room controllers
Table of Contents

Advertisement

SYSTEM
Parameter Name
Reload Default
Version
Parameter Storage
Modbus Registers
Register
Parameter Description
FUNCTION CODE 01 - READ COILS
FUNCTION CODE 05 - WRITE SINGLE COIL
FUNCTION CODE 15 - WRITE MULTIPLE COILS
100
OFF Mode Override
101
ECO Mode Override
102
Heating/Cooling Mode (change-over mode)
FUNCTION CODE 02 - READ DISCRETE INPUTS (Add 10,000 for Modicon Addressing)
100
Digital Input Status (DI1)
101
Boost Status
102
Screen Lock Status
103
Digital Output 1 (TRC-P-1A2T)
104
Digital Output 2 (TRC-P-1A2T)
FUNCTION CODE 04 - READ INPUT REGISTERS (Add 30,000 for Modicon Addressing)
100
Built-In Temperature Measurement
101
Remote Sensor 1 Measurement (Resistive
Input 1)
102
Remote Sensor 2 Measurement (Resistive
Input 2)
103
Current Calculated Setpoint
104
Device Current Mode
105
Relative Humidity Measurement
106
CO2 Measurement
107
Analogue Output Y1
108
Analogue Output Y2
109
Analogue Output Y3
110
Alarm 1 State
111
Alarm 2 State
114
Analogue Input 1 (RI1) Measurement (0-10V,
Option)
115
Analogue Input 2 (RI2) Measurement (0-10V,
Option)
Web-site: www.produal.com
Enquiries: T: +358 10 219 9100 E: info@produal.fi
Description
Reload Default Settings
Software Version
The configuration parameters are stored in the non-volatile memory. When the changes are carried
out via the display, the parameters are stored in the non-volatile memory when the controller returns
to a normal display mode. If the changes are carried out over the network (Modbus or BACnet), then
"NonVol Update" register/object is required to be forced on to save the changes. The register will
automatically return to normal state
The controller supports the following Modbus registers and function codes. The default
communication speed is 9600 bps, 8 data bits, Parity None and 1 Stop Bit. The default Modbus Slave
address is 1. The device Parity can be changed between Odd, None and Even. The baud rate is
selectable between 9600, 19200, 38400, 57600 and 76800 bps. The table shows the register offsets
starting from 0 (0 Base) register address. For example, the Temperature is read from Modbus register
0 using Function Code 04. Some Modbus masters will require one to be added to Modbus registers
(i.e. 1 Base). In this case Function Code 04, register 101 needs to be entered.
Data Type
Signed 16
Signed 16
Signed 16
Signed 16
Unsigned 16
Unsigned 16
Unsigned 16
Unsigned 16
Unsigned 16
Unsigned 16
Unsigned 16
Unsigned 16
Unsigned 16
Unsigned 16
Range
0 = Off (default)
1 = On
x.xx (BACnet/Modbus)
Raw Data
0..1
0..1
0..1
0..1
0..1
0..1
0..1
0..1
-400...3020
-400...3020
-400...3020
-400...3020
0..3
0..1000
0..5000
0..1000
0..1000
0..1000
0..3
0..3
0..1000
0..1000
Copyright © 2020 Produal Oy - All rights reserved - 07/2020
Produal Oy
Range
Off - On
Off - On
0 = Heating, 1 = Cooling
Off - On
Off - On
Off - On
Off - On
Off - On
-40.0...150.0°C
(-40.0..302.0°F)
-40.0...150.0°C
(-40.0..302.0°F)
-40.0...150.0°C
(-40.0..302.0°F)
-40.0...150.0°C
(-40.0..302.0°F)
0 = Comfort
1 = ECO
2 = OFF
3 = Boost
0..100.0 %rH
0..5,000 ppm
0..100.0 %
0..100.0 %
0..100.0 %
0 = Normal (No Alarm)
1 = Amber Alarm
2 = Red Alarm
0 = Normal (No Alarm)
1 = Amber Alarm
2 = Red Alarm
0..100.0 %
0..100.0 %
PS 6001TRC-P - 22/34