Produal TRC-P Series Manual page 10

Touchscreen room controllers
Table of Contents

Advertisement

ECO Mode
ECO MODE TEMPERATURE CONTROL
100%
OFF Mode
Web-site: www.produal.com
Enquiries: T: +358 10 219 9100 E: info@produal.fi
The device can be switched to ECO mode via network, via
digital input (e.g. PIR) or via the touchscreen.
In the ECO mode the controller starts to control to ECO
Heating/Cooling Deadzone and the user setpoint
adjustment (SPA) is removed.
In the ECO mode the CO2 and Humidity loops are
switched to 0%.
The ECO mode can be selected/and cancelled using the
MODE BUTTON (if enabled), The ECO mode is also
indicated by the not showing the setpoint adjustment
buttons.
0%
-
calcSP= Calculated Setpoint (Default 21°C/70°F)
eHDz = ECO Mode Heating Deadzone
eCDz = ECO Mode Cooling Deadzone
(Default 4.0°C/9.2°F)
Note: If the 7 Day Schedule has been activated, the device starts to use the operating mode set at the
next switching point (e.g. if the next switching point is COMFORT MODE, the devices returns to
COMFORT mode).
The controller can be switched to OFF mode via digital
volt-free input (e.g. PIR), via the MODE BUTTON or
via the communication network (system configuration).
In the OFF mode all temperature/CO2/humidity control
outputs are switched off to 0% level.
When in OFF mode if the temperature drops below the
OFF FROST Setpoint, the frost protection is activated,
the SNOWFLAKE icon is displayed on the screen and
the heating stages are switched to 100% and the fan
speed output is switched to 33%. When the
temperature exceeds the OFF FROST setpoint plus 2
degrees, the frost condition is deactivated.
OFF MODE TEMPERATURE CONTROL
100%
Note: In frost condition the
Fan Demand is set @ 33%.
0%
-
2°C /
3.6°F
fSP = Frost Setpoint (Default 8°C / 46°F)
fSP
Note: If the 7 Day Schedule has been activated, the device starts to use the operating mode set at the
next switching point (e.g. if the next switching point is COMFORT MODE, the devices returns to
COMFORT mode).
calcSP
CDz
HDz
eHDz
eCDz
ECO Deadzone
nSP= Nominal Setpoint (Default 21°C / 70°F)
nSP
Copyright © 2020 Produal Oy - All rights reserved - 07/2020
ECO MODE
INDICATION
Target
21
AUTO
Room
20
°C
.1
MEASURED
TEMPERATURE
OFF MODE
INDICATION
Target
8
DIMMED
SCREEN AND
OFF SETPOINT
A
DISPLAY
Room
22
°C
.7
+
MEASURED
TEMPERATURE
PS 6001TRC-P - 10/34
Produal Oy
°C
.5
+
°C
.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

6001trc-p