Inputs And Outputs; Parameter Name - Produal TRC-P Series Manual

Touchscreen room controllers
Table of Contents

Advertisement

INPUTS & OUTPUTS

Parameter Name

Room Sensor Text
Floor Sensor Text
Aux. Sensor Text
Humidity Display
Digital Input Mode
Digital Input Delay
RI1 Mode
RI2 Mode
Aux. Loop Source
Internal Sensor Cal.
RI1 Cal.
RI2 Cal.
CO2 Cal.
Web-site: www.produal.com
Enquiries: T: +358 10 219 9100 E: info@produal.fi
Description
Description for the Room Sensor (Built-In Sensor /
RI1/RI2)
Description for the Floor Sensor (RI1/RI2)
Default; 2 = Floor
Note: Disabled removes Floor Sensor Text and
Measurement from Display. The device may require
Soft Reset after setting 'Disabled'. This is done by
entering and exiting the System configuration menu.
Description for the Aux Sensor (RI1 / RI2 / Network
Value)
Default; 3 = Outside
Note: Disabled removes Aux Sensor Text and
Measurement from Display. The device may require
Soft Reset after setting 'Disabled'. This is done by
entering and exiting the System configuration menu.
Enable / Disable Humidity Display (if option fitted)
Digital Input Operation
Digital Input Delay Timer (transition from active to
non-active)
Resistive Input 1 Mode
Resistive Input 2 Mode
Source for the Auxiliary Loop Sensor (Display
activated when valid temperature is sent)
Internal Sensor One Point Compensation
Sensor Connected to RI1 Calibration
Sensor Connected to RI1 Calibration
CO2 Sensor Calibration (CO2 Models)
Copyright © 2020 Produal Oy - All rights reserved - 07/2020
Produal Oy
Range
1 = Room (Default)
2 = Floor
3 = Outside
4 = Zone 1
5 = Zone 2
6 = Zone 3
7 = Bathroom
8 = Sauna
9 = Bedroom
10 = Kitchen
11 = Cooler
12 = Flow
13 = Hot Water
14 = Tank
15 = Pool
16 = Cabin
0 = Disabled
1 = Room
2 = Floor
3 = Outside
4 = Zone 1
5 = Zone 2
6 = Zone 3
7 = Bathroom
8 = Sauna
9 = Bedroom
10 = Kitchen
11 = Cooler
12 = Flow
13 = Hot Water
14 = Tank
15 = Pool
16 = Cabin
0 = Disabled
1 = Enabled (default)
0 = Close for ECO (Default)
1 = Open for ECO
2 = Close for OFF
3 = Open for OFF
4 = Heating/Cooling Change-Over
5 = Disable Cooling
6 = Contact Alarm
7 = Network Measurement
8 = Close for BOOST
9 = Open for BOOST
0..28,800 seconds (Default 0s)
0 = Disabled (default)
1 = Room (NTC10 Temp Control)
2 = Floor (NTC10 Floor Low/High
Limit Control)
3 = Aux. Loop
4 = Network NTC10
5 = Network 0-10V
6 = CO2; 0..2000ppm = 0-10V
(AI-option)
7 = Main Loop (Control Temp;
0..50°C = 0-10V; AI-option)
8 = Close for ECO (DI-mode)
9 = Open for ECO (DI-mode)
10 = Close for OFF (DI-mode)
11 = Open for OFF (DI-mode)
0 = Built-In Sensor
1 = Network Temp
-10.0..+10.0 °C/°F
-10.0..+10.0 °C/°F
-10.0..+10.0 °C/°F
-500...+500 ppm
PS 6001TRC-P - 19/34