Register
Parameter Description
167
Zone 2 Floor Sensor Text
Default: 2 = Floor
168
Zone 3 Outside Sensor Text
Default: 3 = Outside
169
Alarm 1 Source
170
Alarm 1 Amber Switching Point
171
Alarm 1 Red Switching Point
172
Alarm 1 Hysteresis
173
Alarm 2 Source
174
Alarm 2 Amber Switching Point
175
Alarm 2 Red Switching Point
176
Alarm 2 Hysteresis
177
Override Lights
Notes: After overriding the level the parameter
returns to 0. The lights object takes the last
action (network or user).
Notes: Override Level 1 is the next level after
0% and depends on the configuration. For
On/Off = 100%, for 3-levels = 50%, for 4-levels
= 33%. And so on.
178
Override Blinds
Notes: After overriding the level the parameter
returns to 0. The blinds object takes the last
action (network or user).
Notes: Override Level 1 is 100% for On/Off
config, 25% for 4-steps config.
179
Override Lock Mode
Notes: After overriding the Lock to On/Off the
parameter returns to 0.
180
Maintenance Mode Password
181
Staff Code
182
PWM1 Cycle (Only TRC-P-1A2T/3R2T)
183
Digital Output 1 Network Override (Overrides
DO1 directly, local, only TRC-P-1A2T)
184
Digital Output 2 Network Override (Overrides
DO2 directly, local, only TRC-P-1A2T)
185
Heating/Cooling Changeover Min Temperature
186
Heating/Cooling Changeover Max Temperature
187
Fan Speed Override
Web-site: www.produal.com
Enquiries: T: +358 10 219 9100 E: info@produal.fi
Data Type
Raw Data
Unsigned 16
0..16
Unsigned 16
0..16
Unsigned 16
0..3
Unsigned 16
0..5000
Unsigned 16
0..5000
Unsigned 16
0..5000
Unsigned 16
0..3
Unsigned 16
0..5000
Unsigned 16
0..5000
Unsigned 16
0..5000
Unsigned 16
0..5
Unsigned 16
0..5
Unsigned 16
0..2
Unsigned 16
0..9999
Unsigned 16
0..9999
Unsigned 16
0..120
Unsigned 16
0..2
Unsigned 16
0..2
Unsigned 16
0...950
Unsigned 16
0...950
Unsigned 16
0..7
Copyright © 2020 Produal Oy - All rights reserved - 07/2020
Produal Oy
Range
0 = Disabled
1 = Room
2 = Floor
3 = Outside
4 = Zone 1
5 = Zone 2
6 = Zone 3
7 = Bathroom
8 = Sauna
9 = Bedroom
10 = Kitchen
11 = Cooler
12 = Flow
13 = Hot Water
14 = Tank
15 = Pool
16 = Cabin
0 = CO2
1 = Room (Temperature)
2 = Humidity
3 = None (Default)
0..5000 (Default 0)
0..5000 (Default 0)
0..5000 (Default 0)
0 = CO2
1 = Room (Temperature)
2 = Humidity
3 = None (Default)
0..5000 (Default 0)
0..5000 (Default 0)
0..5000 (Default 0)
0 = None (default)
1 = Override Level (0%)
2 = Override Level 1
(100%-On/Off, 50%-3 Levels, 33%
- 4 Levels)
3 = Override Level 2
(100%-3-Levels, 66% - 4 Levels)
4 = Override Level 3
(100% - 4 Levels)
0 = None (default)
1 = Override Level 0 (0%)
2 = Override Level 1 (25/100%)
3 = Override Level 2 (50%)
4 = Override Level 3 (75%)
5 = Override Level 4 (100%)
0 = None (default)
1 = Override On
2 = Override Off
0000...9999 (default 6666)
0000...9999 (default 0000)
0..120 None (default 30, 0=on/off)
0 = No Override (Default)
1 = Override Output On
2 = Override Output Off
0 = No Override (Default)
1 = Override Output On
2 = Override Output Off
0.0...95.0°C/°F (Default 20°C)
0.0...95.0°C/°F (Default 25°C)
0 = Auto
1 = Manual Off
2 = Manual Level 1
3 = Manual Level 2
4 = Manual Level 3
5 = Manual Level 4
6 = Manual Level 5
7 = Manual Level 6
PS 6001TRC-P - 26/34