Produal TRC-P Series Manual page 23

Touchscreen room controllers
Table of Contents

Advertisement

Register
Parameter Description
116
Fan Speed Demand
117
Thermic1 Demand
118
Thermic2 Demand
200
Firmware Versions
FUNCTION CODE 03 - READ HOLDING REGISTERS (For Modicon Addressing Add 40,000)
FUNCTION CODE 06 - WRITE SINGLE HOLDING REGISTER
FUNCTION CODE 16 - WRITE MULTIPLE HOLDING REGISTERS
100
Nominal Setpoint
101
Heating Comfort Deadzone
102
Cooling Comfort Deadzone
103
ECO Heating Deadzone
104
ECO Cooling Deadzone
105
Frost Setpoint
106
Setpoint Adjust Minimum
107
Setpoint Adjust Maximum
108
Temperature Control Proportional Band
109
Temperature Control Integral Action Time
110
Number of Heating Stages
111
Heating Stage 1 Direction
112
Heating Stage 2 Direction
113
Number of Cooling Stages
114
Cooling Stage 1 Direction
115
Cooling Stage 2 Direction
116
High Limit Setpoint
117
Low Limit Setpoint
118
Limit Ratio
119
CO2 Control Setpoint
120
CO2 Proportional Band
121
CO2 Control Integral Action
122
CO2 Output Direction
123
Humidity Control Setpoint
124
Humidity Proportional Band
125
Humidity Control Integral Action
126
Humidification Output Direction
127
De-Humidification Output Direction
128
Fan Speed Display
Web-site: www.produal.com
Enquiries: T: +358 10 219 9100 E: info@produal.fi
Data Type
Raw Data
Unsigned 16
0..1000
Unsigned 16
0..1000
Unsigned 16
0..1000
Unsigned 16
N/A
Unsigned 16
0...950
Unsigned 16
0...250
Unsigned 16
0...250
Unsigned 16
0...250
Unsigned 16
0...250
Unsigned 16
0...950
Signed 16
-200..0
Signed 16
0..200
Unsigned 16
10...500
Unsigned 16
0..1200
Unsigned 16
0..2
Unsigned 16
0..1
Unsigned 16
0..1
Unsigned 16
0..2
Unsigned 16
0..1
Unsigned 16
0..1
Unsigned 16
0...950
Unsigned 16
0...950
Unsigned 16
0..50
Unsigned 16
0..5,000
Unsigned 16
10..5,000
Unsigned 16
0..10,000
Unsigned 16
0..1
Unsigned 16
0..1000
Unsigned 16
10..1000
Unsigned 16
0..10,000
Unsigned 16
0..1
Unsigned 16
0..1
Unsigned 16
0..5
Copyright © 2020 Produal Oy - All rights reserved - 07/2020
Produal Oy
Range
0..100.0 %
0..100.0 %
0..100.0 %
N/A
0.0...95.0°C/°F
(Default 20°C)
0.0...25.0°C/°F
(Default 0.5°C)
0.0...25.0°C/°F
(Default 0.5°C)
0.0...25.0°C/°F
(Default 4.0°C)
0.0...25.0°C/°F
(Default 4.0°C)
0.0...95.0°C/°F
(Default 8°C)
-20.0..0.0 °C/°F (Default -3.0)
0.0..20.0 °C/°F (Default 3.0)
1.0...50.0°C/°F
(Default 4°C)
0..1200 seconds (600s default)
0 = None
1 = 1-Stage (Default)
2 = 2-Stages
0 = Reverse (Default)
1 = Direct
0 = Reverse (Default)
1 = Direct
0 = None
1 = 1-Stage (Default)
2 = 2-Stages
0 = Reverse
1 = Direct (Default)
0 = Reverse
1 = Direct (Default)
0..95°C/°F (Default 35.0°C)
0..95°C/°F (Default 16.0°C)
0.0..5.0 (0.0=Disabled, Default)
0..5000ppm (Default 1,000 ppm)
10..5000 ppm (Default = 300 ppm)
0..10,000 seconds (Default 0)
0 = Reverse Acting
1 = Direct Acting (Default)
0.0...100.0 %rH (Default 50%)
1.0...100.0 %rH (Default 20.0%)
0..10,000 seconds (Default 0)
0 = Reverse Acting
1 = Direct Acting (Default)
0 = Reverse Acting
1 = Direct Acting (Default)
0 = No Display (Default)
1 = Display Only (no user adj.)
2 = 0 - 1 (0%, 100%)
3 = 0 - 1 - 2 (0%, 50%, 100%)
4 = 0 - 1 - 2 - 3 (0%, 33%,
66%,100%)
5 = 0 - 1 - 2 - 3 - 4 - 5 - 6