HDK - Duct CO
transmitter / controller
2
User Guide
This user guide is for devices with the software version 1.0.10 or newer.

Advertisement

Table of Contents
loading

Summary of Contents for Produal HDK

  • Page 1 HDK - Duct CO transmitter / controller User Guide This user guide is for devices with the software version 1.0.10 or newer.
  • Page 2: Table Of Contents

    Contents 1 Commissioning................3 1.1 Wiring........................3 1.2 Selecting information to be viewed on the display............3 1.3 Calibration.........................3 1.4 ML-SER tool......................4 1.4.1 Connecting ML-SER tool to the device............... 4 1.4.2 ML-SER menu....................4 2 Modbus..................12 2.1 Modbus properties....................12 2.2 Terminating Modbus....................12 2.3 Modbus function codes.....................
  • Page 3: Commissioning

    The automatic calibration function can be deactivated in continuously occupied spaces by using ML-SER tool. Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com Information is subject to change without prior notice.
  • Page 4: Ml-Ser Tool

    Note: The default relay CO set point is 2500 ppm in 10K models. Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com Information is subject to change without prior notice.
  • Page 5 [10...100] The diagram continues on the next page. Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com Information is subject to change without prior notice. EN - 1135050ug...
  • Page 6 Offset: CO2ppm ABC-Logic Offset: °C Offset: %RH Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com Information is subject to change without prior notice. EN - 1135050ug...
  • Page 7 The control output can be controlled either according to a one measurement value or according to the maximum selection of all values. Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com Information is subject to change without prior notice.
  • Page 8 Proportional band for temperature (°C). The value can be adjusted by 0,1 °C steps. Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com Information is subject to change without prior notice.
  • Page 9 Relay menu is available if HD-R option is installed. The relay switching point and hysteresis can be changed through the menu. Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com Information is subject to change without prior notice.
  • Page 10 You can check the device software version and reset the device to factory settings through the menu. Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com Information is subject to change without prior notice.
  • Page 11 / yes Reset to factory settings. Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com Information is subject to change without prior notice. EN - 1135050ug...
  • Page 12: Modbus

    Write Multiple Registers 0x17 Read/Write Multiple Registers Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com Information is subject to change without prior notice. EN - 1135050ug...
  • Page 13: Modbus Registers

    Y4 output voltage Unsigned 16 0...1000 0,00…10,00 V Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com Information is subject to change without prior notice. EN - 1135050ug...
  • Page 14: Holding Registers

    1. 2...10 V 2. 0...5 V Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com Information is subject to change without prior notice. EN - 1135050ug...
  • Page 15 *) The default relay CO set point is 2500 ppm in 10K models. Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com Information is subject to change without prior notice.