Cleaning Mode; Mode Buttons - Produal TRC-P Series Manual

Touchscreen room controllers
Table of Contents

Advertisement

Humidity Control Loop
Operation (-RH option)

Cleaning Mode

Lock Mode
Lock Mode Options
DISABLED
ON/OFF ONLY
ADJUST ONLY
NO INPUT
Remote Sensor RI1 and RI2
Inputs
Web-site: www.produal.com
Enquiries: T: +358 10 219 9100 E: info@produal.fi
Proportional + Integral control by changing the Integral Action Time from 0 to a required value. The
actuator direction can be changed via Output Direction parameter (Direct, Reverse).
In the OFF mode the CO2 loop output is set to 0%. In the ECO mode the CO2 loop operates as in the
day mode.
VAV Maximum Demand
Each of the analogue outputs can also be configured as "Maximum VAV Demand". In this case the
corresponding output (Y1, Y2, Y3) takes the maximum of the CO2 Loop and Cooling Temperature
Loop demand output. This is typically used in demand based ventilation (VAV) to control fresh air
damper when there is either demand for more fresh air, or demand for temperature cooling (typically
fresh air cools down the room space).
Maximum Fan Demand
Each of the analogue outputs can be configured ad "Maximum Fan Demand". In this configuration the
corresponding output (Y1, Y2, Y3) takes the maximum demand of the CO2 Control Loop and Fan
Speed Control Loop. This can provide fan speed boost at high CO2 level and when the fan speed
temperature loop has increased the demand.
The RH models can measure and control
the relative humidity level. This can then be
used in demand based control applications
to increase the fresh air supply e.g. in the
high humidity conditions. The control loop
has both de-humidification and
humidification outputs that can be linked to
any of the physical control outputs Y1, Y2,
or Y3. The direction of the both outputs can
also be reversed to driver the actuators
100-
0% instead of 0-100%.
After entering FURTHER INFORMATION screen, by selecting the CLEANING icon, it is possible to
activate the cleaning mode. The TRC will enter a "Clean Screen" state where all touchscreen presses
are ignored and 30 second countdown timer is displayed. This allows cleaning of the device itself.
After entering FURTHER INFORMATION screen, by selecting the
LOCK icon it is
possible to lock the device. Now by entering the
LOCK CODE, the device lock state can be activated.
The lock mode can be configured to work in different ways as
described at the below table.
DISABLED: Lock Mode Icon Not Available
ON/OFF ONLY: Allows Mode Buttons Only
ADJUST ONLY: Allows Temperature Adjustment Only
NO INPUT: All Buttons Locked
If the lock code is set to 0000 (default), there is no need to enter the
lock code and the lock entry screen is bypassed.
Lock
Up and Down
NO
YES
YES
NO
YES
YES
YES
NO
A remote NTC10k3 sensor can be connected to the RI1 and RI2 inputs to be used for different control
and display purposes. The options are:-
DISABLED; the measurement is disabled
ROOM; the input is used for the main temperature control loop
FLOOR; the input is used for High/Low Limit Control
OUTSIDE: the input is used to show the Outside Temperature
NETWORK NTC10; the resistive input is available over the communication network as tempera-
ture.
NETWORK 0-10V; the input is used as 0.10V network monitoring input (requires AI option)
CO2; the input is used as CO2 0..10Vdc measurement for CO2 control (requires AI option)
MAIN LOOP; the 0..10Vdc voltage is used for the main temperature control (requires AI option)
LOOP OUTPUT
100%
0%
-
0%rH
SP= Setpoint e.g. 50%rH
Icon Active / Visible
OFF
Fan Speed
YES
YES
YES
NO
NO
NO
NO
NO
Copyright © 2020 Produal Oy - All rights reserved - 07/2020
Produal Oy
Humidity %rH
100%rH
+
Proportional Band
SP
e.g 5%rH
Lock Code
Enter Code
0000
7
8 9
4
5 6 -
1
2 3
Esc
0
Del
OK

Mode Buttons

YES
YES
NO
NO
PS 6001TRC-P - 13/34