Produal TRC-P Series Manual page 21

Touchscreen room controllers
Table of Contents

Advertisement

FAN, BOOST, TIMES
Parameter Name
Mode Button
ALARMS
Parameter Name
Alarm 1 Source
Alarm 1 Amber Threshold
Alarm 1 Red Threshold
Alarm 1 Hysteresis
Alarm 2 Source
Alarm 2 Amber Threshold
Alarm 2 Red Threshold
Alarm 2 Hysteresis
SYSTEM
Parameter Name
Address
Baud Rate (Only Modbus/BACnet versions)
Parity (Only Modbus/BACnet versions)
Stop Bits (Only Modbus/BACnet versions)
Device ID (Only BACnet versions)
Service Pin (Only BACnet versions)
Brightness
Show Unit Swap
Lock Mode
Lock Code
Maintenance Code
Staff Code
Language
Native Units (Defaults)
Auto Daylight Savings
Screen Cycle Speed
Screen Refresh Rate
Web-site: www.produal.com
Enquiries: T: +358 10 219 9100 E: info@produal.fi
Description
COMFORT / ECO / OFF / BOOST Button Mode
Operation Mode
Description
Source for the Alarm Display
Alarm 1 Amber Backlight Switching Point
Alarm 1 Amber Backlight Switching Point
Hysteresis for Alarm 1
Source for the Alarm Display
Alarm 2 Amber Backlight Switching Point
Alarm 2 Amber Backlight Switching Point
Hysteresis for Alarm 2
Description
Modbus Address (Only Modbus versions)
BACnet MAC Address (Only BACnet versions)
Modbus / BACnet Baud Rate
Parity
Stop Bits
BACnet Device ID
Bacnet Service Pin (when activated the device
sends BACnet I-AM message)
Backlight Brightness
Shows the Fahrenheit / Celcius Unit Selection
Button
Lock Operation
Lock Mode Password
Maintenance Mode Password
Staff Page Password - Access Password to Further
Settings Screen
Language
Selects either Fahrenheit / Celsius as Native Units
NOTE: RELOADS DEFAULTS
Automatic Summer/Winter Time Adjustment
Cycle Speed of Measurements in the ACTION RING
Fast = 4.3 secs, Medium = 7.8 secs, Slow = 10.8
secs
Refresh Rate of the LCD Screen
Copyright © 2020 Produal Oy - All rights reserved - 07/2020
Produal Oy
Range
0 = Active (Default)
1 = Indication Only
Range
0 = CO2 Sensor
1 = Room (Temperature)
2 = Humidity
3 = None (Default)
0..5000 (Default 0)
0..5000 (Default 0)
0..5000 (Default 0)
0 = CO2 Sensor
1 = Room (Temperature)
2 = Humidity
3 = None (Default)
0..5000 (Default 0)
0..5000 (Default 0)
0..5000 (Default 0)
Range
0..247 (Default 1)
0..127 (Default 1)
0 = 9600 (Default)
1 = 19200
2 = 38400
3 = 57600
4 = 76800
0 = None (Default)
1 = Odd
2 = Even
0 = 1 Stop Bit (Default)
1 = 2 Stop Bits
0..4,194,303
(Default Auto=651001)
0 = Disabled (default)
1 = Enabled
0..20 (default 5)
0 = Disabled (default)
1 = Enabled
0 = Disabled (default)
1 = On /Off Only (Lights & Blinds)
2 = Temp Adjust Only Available
3 = No Input - All Buttons Disabled
0000 - 9999 (default 0000)
0000 - 9999 (default 6666)
0000 - 9999 (default 0000 =
disabled)
EN = English (Default)
FR = French
C = Celsius (default)
F = Fahrenheit
0 = Disabled (default)
1 = Enabled
0 = Fast
1 = Medium (default)
2 = Slow
0 = Fast (default)
1 = Medium
2 = Slow
PS 6001TRC-P - 21/34