Produal TRC-P Series Manual page 25

Touchscreen room controllers
Table of Contents

Advertisement

Register
Parameter Description
148
Digital Input Mode
149
Digital Input Delay
150
Internal Sensor Calibration
151
RI1 Calibration
152
RI2 Calibration
153
CO2 Calibration
154
Humidity Calibration
155
Lock Mode
156
Lock Mode Password
157
Boost Time
158
Boost Target
159
Boost Target Value
160
Mode Display Button
163
Brightness (Backlight Level)
164
Display Humidity
165
Show Swap Temperature Units Icon
166
Zone 1 Room Sensor Text
Web-site: www.produal.com
Enquiries: T: +358 10 219 9100 E: info@produal.fi
Data Type
Raw Data
Unsigned 16
0..9
Unsigned 16
0..28,800
Signed 16
-100..+100
Signed 16
-100..+100
Signed 16
-100..+100
Signed 16
-500..+500
Signed 16
-100..+100
Unsigned 16
0..4
Unsigned 16
0..9999
Unsigned 16
0..480
Unsigned 16
0..5
Unsigned 16
0..5000
Unsigned 16
0..1
Unsigned 16
0..20
Unsigned 16
0..1
Unsigned 16
0..1
Unsigned 16
0..16
Copyright © 2020 Produal Oy - All rights reserved - 07/2020
Produal Oy
Range
0 = Close for ECO (Default)
1 = Open for ECO
2 = Close for OFF
3 = Open for OFF
4 = Heating/Cooling Change-Over
5 = Disable Cooling
6 = Contact Alarm
7 = Network Measurement
8 = Close for BOOST
9 = Open for BOOST
0..28,800 seconds (Default 0s)
-10.0..+10.0 °C/°F
-10.0..+10.0 °C/°F
-10.0..+10.0 °C/°F
-500...+500 ppm
-10.0..+10.0 % rH
0 = Lock mode disabled (default)
1 = On/Off workable only
2 = Temp settings only available
3 = All buttons disabled
0000...9999
0 = Permanent (Default 0)
1..480 minutes
0 = Nominal SP (Temperature)
1 = CO2 SP
2 = Humidity SP
3 = Dehum SP
4 = Fan Demand
5 = Aux. Temp SP
0...5000 (default 25)
0 = Indication Only
1 = Active (default)
0..20 (default 5)
0 = Disabled
1 = Enabled (default)
0 = Disabled (default)
1 = Enabled
1 = Room (Default)
2 = Floor
3 = Outside
4 = Zone 1
5 = Zone 2
6 = Zone 3
7 = Bathroom
8 = Sauna
9 = Bedroom
10 = Kitchen
11 = Cooler
12 = Flow
13 = Hot Water
14 = Tank
15 = Pool
16 = Cabin
PS 6001TRC-P - 25/34

Advertisement

Table of Contents
loading

This manual is also suitable for:

6001trc-p

Table of Contents