CONTROL SETTINGS

Parameter Name
Nominal SP
Heating DZ COMFORT
Cooling DZ COMFORT
Heating DZ ECO
Cooling DZ ECO
Frost SP
Setpoint Adj. Max.
Setpoint Adj. Min.
PB
IA
Heating Stages
Heating Stage 1 Dir.
Heating Stage 2 Dir.
Cooling Stages
Cooling Stage 1 Dir.
Cooling Stage 2 Dir.
Aux. SP
Aux. PB
Aux. IA
Aux Dir.
CO2 SP
CO2 PB
CO2 IA
Humidity SP
Humidity PB
Humidity IA
Limit High
Limit Low
Limit Ratio
Changeover Low
Changeover High
Web-site: www.produal.com
Enquiries: T: +358 10 219 9100 E: info@produal.fi
NOTE:The maintenance mode password can be changed in the configuration settings. Make
sure that you note the new password if changed. If the Maintenance Code is set as 0000, the
Maintenance Code entry screen is bypassed (i.e. no protection).
NOTE:It is good practice to reset the device after the configuration has been completed. Soft
reset is automatically carried out after entering and exiting System configuration menu, or
alternative power cycle the device.
Description
Nominal Setpoint (Temperature Control)
Heating Deadzone in COMFORT mode
Cooling Deadzone in COMFORT mode
Heating Deadzone in ECO Mode
Cooling Deadzone in ECO Mode
Night Frost Setpoint (OFF Mode)
Temperature Setpoint Maximum Adjustment
Temperature Setpoint Minimum Adjustment
Temperature Control Proportional Ban
Integral Action time of the temperature control loop.
Set to 0 to disable.
Number of Heating Stages
Heating Stage 1 Direction
Heating Stage 2 Direction
Number of Cooling Stages
Cooling Stage 1 Direction
Cooling Stage 2 Direction
Auxiliary Heating Control Loop Setpoint
Auxiliary Heating Control Loop Proportional Band
Auxiliary Heating Control Loop Integral Action
Auxiliary Control Loop Actuator Direction (actuator
direction, Direct = 0..100%, Reverse = 100..0%)
CO2 Setpoint
CO2 Proportional Band
Integral Action time of the CO2 control loop. Set to 0
to disable.
Humidity Setpoint
Humidity Proportional Band
Integral Action time of the humidity control loop. Set
to 0 to disable.
High Limit Setpoint; High Limit Control
Low Limit Setpoint; Low Limit Control
Low/High Limit Ratio
Note: 0.0 setting disables the reset control.
Low Limit where the TRC Automatically Switches to
Cooling Mode (Cold water supplied)
High Limit where the TRC Automatically Switches to
Heating Mode (Hot water supplied)
Range
0.0...95.0°C/°F (Default 21.0°C)
0.0...25.0°C/°F (Default 0.5°C)
0.0...25.0°C/°F (Default 0.5°C)
0.0...25.0°C/°F (Default 4.0°C)
0.0...25.0°C/°F (Default 4.0°C)
0.0...95.0°C/°F (Default 8.0°C)
0.0...20°C/°F (Default 3.0)
-20.0...0°C/°F (Default -3.0)
1.0..50.0 °C/°F (Default 4.0)
0..1,200 seconds (Default 600s)
0 = None
1 = 1-Stage (Default)
2 = 2-Stages
0 = Reverse (Default)
1 = Direct
0 = Reverse (Default)
1 = Direct
0 = None
1 = 1-Stage (Default)
2 = 2-Stages
0 = Reverse
1 = Direct (Default)
0 = Reverse
1 = Direct (Default)
0.0...95.0°C/°F (Default 21.0°C)
1.0..50.0 °C/°F (Default 4.0)
0..1,200 seconds (Default 600s)
0 = Reverse Acting
1 = Direct Default)
0..5000ppm (Default 1,000 ppm)
10..5000 ppm (Default = 300 ppm)
0..10,000 seconds (Default 0)
0.0...100.0 %rH (Default 50%)
0.1...100.0 %rH (Default 20.0%)
0..10,000 seconds (Default 0)
0.0..95.0°C/°F (Default 35.0°C)
0.0..95.0°C/°F (Default 16.0°C)
0.0..5.0 (0.0=Disabled, Default)
0.0..95.0°C/°F (Default 20.0°C)
0.0..95.0°C/°F (Default 25.0°C)