Produal TRC-P Series Manual page 30

Touchscreen room controllers
Table of Contents

Advertisement

App_Config Objects
Property Name /ID
Required
Object Identifier
Object
Object Name
Properties
Object Type
Optional
None
Properties
Property ID
Proprietary
40106
Properties
40107
40110
40111
40112
40113
40114
40115
40116
40117
40118
40120
40121
40122
40124
40125
40126
40127
40128
Web-site: www.produal.com
Enquiries: T: +358 10 219 9100 E: info@produal.fi
Note1: Objects are used to change the mode ON or OFF. The mode takes the last action e.g. after
overriding the ECO mode on via BO(1), the user can cancel the ECO mode from the screen. The
present value field indicates the current state.
Note2: RO = "Read Only". Not possible to write to the object.
Note3: It is possible to override the output level without changing the Y1/Y2/Y3 mode to network. The
object returns to use the internal logic value once the priority inputs have been set to 'null'.
NOTE: Application Configuration Objects expose the configuration parameters over the
BACnet. However please check if your BACnet client can support Proprietary Object types to
be able to access these parameters. Alternatively set the configuration parameters through the
TRC touchscreen.
Attributes
R
R/W
R
Description
Setpoint Adjust Minimum
Setpoint Adjust Maximum
Number of Heating Stages
Heating Stage 1 Direction
Heating Stage 2 Direction
Number of Cooling Stages
Cooling Stage 1 Direction
Cooling Stage 2 Direction
High Limit Setpoint
Low Limit Setpoint
Limit Ratio
CO2 Proportional Band
CO2 Control Integral Action
CO2 Output Direction
Humidity Proportional Band
Humidity Control Integral Action
Humidification Output Direction
De-Humidification Output Direction
Fan Speed Display
Range
Default
proprietary-128
"Config1"
proprietary-128
BACnet Data Type
Range
REAL
-20.0..0.0 °C/°F (Default -3.0)
REAL
0.0..20.0 °C/°F (Default 3.0)
Unsigned
0 = None
1 = 1-Stage (Default)
2 = 2-Stages
Unsigned
0 = Reverse (Default), 1 = Direct
Unsigned
0 = Reverse (Default), 1 = Direct
Unsigned
0 = None
1 = 1-Stage (Default)
2 = 2-Stages
Unsigned
0 = Reverse, 1 = Direct (Default)
Unsigned
0 = Reverse, 1 = Direct (Default)
REAL
0..95°C/°F (Default 35.0°C)
REAL
0..95°C/°F (Default 16.0°C)
REAL
0.0..5.0 (0.0=Disabled, Default)
Unsigned
10..5000 ppm (Default = 300 ppm)
Unsigned
0..10,000 seconds (Default 0)
Unsigned
0 = Reverse Acting
1 = Direct Acting (Default)
REAL
1.0...100.0 %rH (Default 20.0%)
Unsigned
0..10,000 seconds (Default 0)
Unsigned
0 = Reverse Acting
1 = Direct Acting (Default)
Unsigned
0 = Reverse Acting
1 = Direct Acting (Default)
Unsigned
0 = No Display (Default)
1 = Display Only (no user adj.)
2 = 0 - 1 (0%, 100%)
3 = 0 - 1 - 2 (0%, 50%, 100%)
4 = 0 - 1 - 2 - 3 (0%, 33%, 66%,100%)
5 = 0 - 1 - 2 - 3 - 4 - 5 - 6
Copyright © 2020 Produal Oy - All rights reserved - 07/2020
Produal Oy
PS 6001TRC-P - 30/34