INPUTS & OUTPUTS
Parameter Name
Humidity Cal.
Y1
Y2
Y3
Y1 Min.
Y1 Max.
Y2 Min.
Y2 Max.
Y3 Min.
Y3 Max.
Anti-JAM
PWM Period
FAN, BOOST, TIMES
Parameter Name
Fan Speed Display
Fan Speed Source
Min Fan Level
Fan Off Delay
Boost Time
Boost Target
Boost Setpoint Value
Web-site: www.produal.com
Enquiries: T: +358 10 219 9100 E: info@produal.fi
Description
Humidity Calibration (RH Models)
Analogue Output Y1 Mode
Default: Modulating Fan
NOTE: With TRC-P-2A3R, 1A4R and 3R2T do
not change this setting - leave to default.
Analogue Output Y2 Mode
Default: Heating Stage 1
TRC-P-1A4R Default: Heating Stat1
NOTE: Not available with TRC-P-1A2T/3R2T.
Analogue Output Y3 Mode
Default: Cooling Stage.
NOTE: Not available with TRC-P-1A2T/3R2T.
Analogue Output Y1 Minimum Value
Analogue Output Y1 Minimum Value
Analogue Output Y2 Minimum Value
Analogue Output Y2 Minimum Value
Analogue Output Y3 Minimum Value
Analogue Output Y3 Minimum Value
Valve Exercise
PWM Period (TRC-P-1A2T/TRC-H-3R2T)
Description
Selecting the Fan Speed (User Adjustment) for the
Display
Note: Modes 2,3,4 set the number of steps the user
can manually adjust the fan speed.
Fan Speed Control Source
(The fan speed follows theselected control loop
output. The minimi Fan Level parameter applies in
operation)
Fan Speed Minimum Active Level
Fan Switch Off Delay when Fan Speed Source
Demand < Min Fan Level.
Note: Only active if Min Fan Level is set.
Boost Mode Running Time
Boost Button Target Operation
Boost Setpoint Value, The target value that the
boost button affects (whole integers).
Copyright © 2020 Produal Oy - All rights reserved - 07/2020
Produal Oy
Range
-10.0..+10.0 % rH
0 = Network Value
1 = Heating Stage 1
2 = Heating Stage 2
3 = Cooling Stage 1
4 = Cooling Stage 2
5 = Modulating Fan (EC)
6 = CO2 Control
7 = Maximum VAV
8 = Maximum Fan
9 = Humidification
10 = De-humidification
11 = Amber / Red
12 = Red
13 = Heating Stage1 Sta
14 = Cooling Stage1 Stat
15 = Fan Stat
16 = Aux Loop
17 = 6-Port (Valve)
18 = 6-Port Reverse (Valve)
0..100%(0% = default)
0..100% (100% = default)
0..100%(0% = default)
0..100% (100% = default)
0..100%(0% = default)
0..100% (100% = default)
0..14 Days (default 0 = disabled)
0..120 Seconds (default 30)
Range
0 = None (Default)
1 = No Input (no user adj.)
2 = 0 - 1 (0%, 100%)
3 = 0 - 1 - 2 (0%, 50%, 100%)
4 = 0 - 1 - 2 - 3 (0%, 33%,
66%,100%)
5 = 0 - 1 - 2 - 3 - 4 - 5 - 6
0 = Heating 1 and Cooling 1 Stage
(Default)
1 = Heating Stage1
2 = Cooling Stage 1
3 = Heating and Cooling Stage 2
4 = Heating Stage 2
5 = Cooling Stage 2
6 = CO2
7 = Humidification
8 = De-Humidification
9 = Maximum VAV (Cooling/CO2)
10 = Maximum Temp/Hum
11 = Aux. Loop
0...100% (Default 0%)
0...28,800 seconds (Default = 0)
0 = Infinite
0 = Permanent
1..480 minutes (Default 0)
0 = Nominal SP (Temperature)
1 = CO2 SP
2 = Humidity SP
3 = Dehum SP
4 = Fan Demand
5 = Aux. Temp SP
0...5000 (default 25)
PS 6001TRC-P - 20/34