Parameterisation - Festo CPX-AP-I-4DI4DO-M12-5P Instructions And Operating

Digital input/output module
Hide thumbs Also See for CPX-AP-I-4DI4DO-M12-5P:
Table of Contents

Advertisement

Parameterisation

9
Parameterisation
Various parameters are available for reading out information about the modules in an automation sys-
tem CPX-AP and adapting the modules to the application situation.
Write access to the parameters is typically performed by the higher-level controller using the device
descriptions specific to the host system.
ID
Parameter
70
Part number
246
Fieldbus serial number
791
Product key
960
Firmware version
20000
Module code
20014
Input debounce time
0: 0.1 ms
1: 3.0 ms (factory setting)
2: 10 ms
3: 20 ms
20022
Configuration of voltage monitoring load
supply PL
0: load voltage monitoring inactive
1: load voltage monitoring active, with
suppression of diagnostics at switch-
off (factory setting)
2: load voltage monitoring active
20052
Behaviour in error state (communication
fault)
0: reset outputs (factory setting)
1: maintain status
20085
Measured value temperature AP-ASIC [°C]
20087
Current measured value of logic supply PS
[mV]
20088
Current measured value of load supply PL
[mV]
20093
Hardware version
1) ro = read only; rw = read write
Tab. 11 Parameter
Festo — CPX-AP-I-4DI4DO-M12-5P — 2019-06
Instance-
Data
s
type
1
UINT32
1
UINT32
1
CHAR
1
CHAR
1
UINT32
4
UINT8
1
UINT8
1
UINT8
1
INT16
1
UINT16
1
UINT16
1
UINT8
Access
Arraysize
1)
ro
ro
ro
12
ro
30
ro
rw
rw
rw
ro
ro
ro
ro
11

Advertisement

Table of Contents
loading