Commissioning
Variant
I/O
4AA-H
Input
Output
1) IW CH0 = actual value of channel 0 (input), SW CH1 = setpoint value of channel 1 (output), etc.; HV= HART variable
Tab. 14 Process image for variants with HART variables
9.3

HART variables

The process image can be extended with a total of 4 HART variables
è Tab. 14 Process image for variants with HART variables.
Quantity per HART variable: 4 bytes
Data format: 16-bit value
Depending on the higher-order control system, low byte and high byte may be organised differ-
ently.
If an invalid value has been determined, 0xFFFF is transmitted.
Determination of the HART variables to be transferred during parameterisation
è 9.4 Parameterisation.
9.4

Parameterisation

The terminal CPX and the module described here can be parameterised with the operator unit (CPX-
MMI), the Festo Maintenance Tool (CPX-FMT) software or the higher-level system.
Festo — CPX-4AE-4AA-H — 2019-04a
Content of bytes
1)
22
20
18
16
14
23
21
19
17
15
HV4
12
10
8
6
4
13
11
9
7
5
HV3
HV2
SW
SW
CH3
CH2
Address
space
2
0
allocation
3
1
HV1
16 bytes
SW
SW
8 bytes
CH1
CH0
29