Flueing Arrangements; Horizontal Termination (Flex) - Regency Fireplace Products Greenfire GF900L Owners & Installation Manual

Table of Contents

Advertisement

installation

FLUEING ARRANGEMENTS

HORIZONTAL TERMINATION (FLEX)

Regency
Direct Vent System
®
These flueing systems, in combination with GF900L, have been tested and listed as a Direct Vent system by AGA. The location of the termination
cap must conform to the requirements in the Flue Terminal Locations diagram from the "Exterior Flue Termination Locations" section.
Regency
Direct Vent (Flex) System Termination Kits includes all the parts needed to install the GF900L using a flexible vent.
®
FPI Kit #
Length
Contains:
#946-515
1.2 m
1)
2)
3)
4)
5)
#946-516
3 m
6)
7)
8)
9)
Notes:
1) Liner sections should be continuous without any
joints or seams.
2) Only Flex pipe purchased from Regency
used for Flex installations
3) Horizontal flue must be supported every 0.9m.
4) Regency
Direct Vent System (Flex) is only approved
®
for horizontal terminations.
5) Flex system can only be used up to a maximum
continuous vent length of up to 3m. If longer runs
are required, rigid pipe must be used.
NOTE: Maximum horizontal run: 3M
20
175mm flexible outer liner (Kit length)
102mm flexible inner liner (Kit length)
spring spacers
thimble
AstroCap termination cap
screws
tube of Mill Pac
plated screws
S.S. screws #8 x 1-1/2" drill point
may be
®
102mm
Flue Guard - if required*
(Part #946-506/P)
Regency GF900L-1 Gas Fireplace