installation
UNIT INSTALLATION WITH
HORIZONTAL TERMINATION

102MM X 175MM FLUEING

(Rigid Flue Systems)
Minimum Flue Clearances
to Combustibles
* Clearances noted below must be maintained;
except when passing through a wall, ceiling or at the
termination where the use of a firestop or wall thimble
reduces clearance to 38mm.
Horizontal Top*
76mm*
Horizontal Side
51mm
Horizontal Bottom
51mm
Vertical Vent
51mm
Below are the recommended framing dimensions
(inside measurements) for the 102mm X 168mm
rigid vent terminations - for use with a wall
thimble.
Recommended Framed Opening Size
Flue Size
Framing Size
102mm x 175mm
254mm x 254mm
Install
the flue
system
according
manufacturer's instructions included with the
components.
1) Set the unit in its desired location. Check to
determine if wall studs or roof rafters are in
the way when the flueing system is attached.
If this is the case, you may want to adjust the
location of the unit. Rough in the gas preferably
on the right side of the unit and the electrical
(junction block is on the left side) on the left.
2) Simpson Dura Vent Flue pipe and fittings are
designed with special twist-lock connections
to connect the flueing system to the appliance
flue outlet. A twist-lock appliance adaptor is
required.
3) In conjunction with the Simpson Direct Vent
Pro system, install the adaptor after the unit
is set in its desired location. Put a bead of Mill
Pac inside the outer section of the adapter and
a bead of Mill Pac on the inner collar. Slip the
adapter over the existing inner and outer flue
collar. Fasten to the outer collar only with the
3 supplied screws (drilling pilot holes will make
this easier).
4) Level the fireplace and fasten it to the framing
using nails or screws through the top and side
nailing strips.
26
5) Assemble the desired combination of pipe and
elbows to the appliance flue outlets and secure.
Note: For best results and optimum
performance with each approved
venting system, it is highly
recommended to apply "Mill-Pac"
sealant to every inner pipe connection.
Failure to do so may result in drafting
or performance issues not covered
under warranty.
Horizontal runs of vent must be supported
every 0.9 metre. Wall straps are available for
this purpose.
6) Mark the wall for a square hole.-see chart to left
for size. The center of the square hole should line
up with the center-line of the horizontal pipe. Cut
and frame the square hole in the exterior wall
where the vent will be terminated. See diagram
2 for center line requirements.
If the wall being penetrated is constructed of
non-combustible material, i.e. masonry block
or concrete, an
acceptable.
Note:
to
the
a) The horizontal run of vent must be level, or
have a 6mm rise for every 305mm of run
towards the termination. Never allow the
vent to run downward. This could cause
high temperatures and may present the
possibility of a fire.
b) The location of the horizontal vent
termination on an exterior wall must meet
all local and national building codes,
center
of hole
C L
"THIS UNIT MUST ALWAYS
TERMINATE / FLUE
DIRECTLY TO THE OUTDOORS."
203mm diameter
hole is
C L
Diagram 2
7) Ensure that the pipe clearances to combustible
materials are maintained (Diagram 5). Install
the termination cap.
Note: If installing termination on a siding
covered wall, a siding standoff or furring
strips must be used to ensure that the
termination is not recessed into the
siding.
Diagram 5
The four wood screws provided should be
replaced with appropriate fasteners for stucco,
brick, concrete, or other types of sidings.
8) Before connecting the horizontal run of vent pipe
to the vent termination, slide the Wall Thimble
over the vent pipe. The wall thimble is required
for all horizontal terminations.
9) Slide the appliance and vent assembly towards
the wall carefully inserting the vent pipe into the
vent cap assembly. It is important that the vent
pipe extends into the vent cap sufficient distance
so as to result in a minimum pipe overlap of
32mm. Secure the connection between the vent
pipe and the vent cap.
10) Install wall thimble in the center of the framed
hole and attach with wood screws (Diagram 7).
Diagram 7
NOTE:
"NOT INTENDED FOR
FIREPLACE INSERT".
Regency GF900L-1 Gas Fireplace