Flueing Arrangements; Horizontal Termination (Flex) - Regency Fireplace Products Greenfire GF900C Owners & Installation Manual

Hide thumbs Also See for Greenfire GF900C:
Table of Contents

Advertisement

FLUEING ARRANGEMENTS

HORIZONTAL TERMINATION (FLEX)

Regency
Direct Vent System
®
These flueing systems, in combination with GF900C, have been tested and listed as a Direct Vent system by AGA. The location of the termination
cap must conform to the requirements in the Flue Terminal Locations diagram from the "Exterior Flue Termination Locations" section.
Regency
Direct Vent (Flex) System Termination Kits includes all the parts needed to install the GF900C using a flexible vent.
®
FPI Kit #
Length
Contains:
1)
#946-515
1.2 m
2)
3)
4)
5)
#946-516
3 m
6)
7)
8)
9)
Notes:
1. Liner sections should be continuous without any joints
or seams.
2. Only Flex pipe purchased from Regency® may be used
for Flex installations
3. Horizontal flue must be supported every 0.9m.
4. Regency® Direct Vent System (Flex) is only approved
for horizontal terminations.
5. Flex system can only be used up to a maximum continu-
ous vent length of up to 3m. If longer runs are required,
rigid pipe must be used.
NOTE: Maximum horizontal run: 3M
Regency GF900C-2 Gas Fireplace
175mm flexible outer liner (Kit length)
102mm flexible inner liner (Kit length)
spring spacers
thimble
AstroCap termination cap
screws
tube of Mill Pac
plated screws
S.S. screws #8 x 1-1/2" drill point
102mm
installation
Flue Guard - if required*
(Part #946-506/P)
25