Combustible Requirements - Regency Fireplace Products Greenfire GF900L Owners & Installation Manual

Table of Contents

Advertisement

FRAMING & FINISHING
Finished
Nailing Strip
Material
Position
12mm
25mm
25mm
12mm
38mm
0mm (flush)

COMBUSTIBLE REQUIREMENTS

Timber Stud
Regency GF900L-1 Gas Fireplace
83mm
Nailing Strip
25mm Forward
Unit
Nailing Strip
12mm Forward
Unit
Nailing Strip
Flush w/unit
Factory Set
Unit
1165mm
Non-combustible
Material
NOTE: A minimum thickness
of 12mm non combustible
facing is required.
Non-combustible
Combustible
Material
Note:
The siding nailing strips are factory set at 12mm. The
top nailing strip is fixed during transit to the rear of the
appliance.
Do not place any reinforcement in front of header and
behind finishing material.
The nailing strip must be used. It is fixed during transit
to the rear of the unit.
Note:
Depending on the material used for finishing, the nailing
strips must be set accordingly so that the finished material
is always at the 38mm edge of the flange.
MINIMUM THICKNESS OF THE FINISH MATERIAL: 12MM
Header
on edge
Timber Stud
installation
NOTE:
The appliance must be installed
on a flat, solid continuous surface,
For example., a wood, metal or
concrete floor or in a raised (on
the wall) application. The appli-
ance must be installed on a metal
or wood base extending the full
width and depth of the appliance.
NOTE:
If raising the unit, then the minimum
height measurement (A) on page
11 of the framing dimensions must
be adhered to. For example., Unit
raised 300mm then A+ 300mm =
1389mm.
15