Keypad Mode (P-12 = 1 Or 2); Modbus Control Mode (P-12 = 3 Or 4) - Invertek Drives Optidrive ODE-2-12005-1H01 01 Series User Manual

Ac variable speed drive for psc & shaded pole single phase motors 0.37 – 1.1kw / 0.5 – 1.5hp ip20 open & ip66 (nema 4x) enclosed units
Table of Contents

Advertisement

Terminal Mode P-12=0, P-15=3
+24 Volt
Run (Enable)
Analog / Preset 1
External Trip
+ 10 Volts
Reference
0 Volts
Analog speed input with 1 preset speed and
motor thermistor trip
7.2.

Keypad Mode (P-12 = 1 or 2)

P-15
Digital input 1 (T2)
0..2
Open: Stop (disable)
5,
Closed: Run (enable)
8..12
Open: Stop (disable)
3
Closed: Run (enable)
Open: Stop (disable)
4
Closed: Run (enable)
Open: Stop (disable)
6
Closed: Run (enable)
Open: Forward Stop
7
Closed: Forward Run
Example Wiring
Keypad Mode P-12=1 or 2, P-15=0
+24 Volt
Run (Enable)
Increase Speed
Reduce Speed
Remote push button speed control
By default if the enable signal is present the drive will not Enable until the START button is pressed. To automatically enable the drive when the
NOTE
enable signal is present set P-31 = 2 or 3. This then disables the use of the START & STOP buttons
7.3.

Modbus Control Mode (P-12 = 3 or 4)

P-15
Digital input 1 (T2)
0..2,
Open: Stop (disable)
4..5,
Closed: Run (enable)
8..12
Open: Stop (disable)
3
Closed: Run (enable)
Open: Stop (disable)
6
Closed: Run (enable)
Open: Stop (disable)
7
Closed: Run (enable)
Further information the MODBUS RTU Register Map information and communication setup; please contact your Invertek Drives
Sales Partner.
Optidrive E2 Single Phase Output User Guide V3.10
Terminal Mode P-12=0, P-15=4
Local or remote analog speeds
(2 analog inputs)
Digital input 2 (T3)
Digital input 3 (T4)
Closed : remote UP push-
Closed : remote DOWN
button
push-button
Closed : remote UP push-
External trip input :
button
Open: Trip, Closed: Run
Closed : remote UP push-
Open : Keypad speed ref
button
Closed : Analog input 1
External trip input :
No Effect
Open: Trip, Closed: Run
Open: Run
External trip input :
Closed: Fast Stop
Open: Trip, Closed: Run
Digital input 2 (T3)
Digital input 3 (T4)
No effect
No effect
Open : Master speed ref
External trip input :
Closed : Preset speed 1
Open: Trip, Closed: Run
Open : Master speed ref
External trip input :
Closed : Analog input
Open: Trip, Closed: Run
Open : Master speed ref
External trip input :
Closed : keypad speed ref
Open: Trip, Closed: Run
www.invertekdrives.com
Terminal Mode P-12=0, P-15=11
+24 Volt
Run (Enable)
Local / Remote
(Hand / Auto)
Remote (Auto)
Reference
+ 10 Volts
Local (Hand)
Reference
0 Volts
Push button fwd/stop/fast stop using 2
Analog input (T6)
Open : Keypad speed ref
+24V : Preset speed 1
Closed : remote DOWN
push-button
Analog input 1
Open : Keypad speed ref
+24V : Preset speed 1
Open : Keypad speed ref
+24V : Preset speed 1
Analog input (T6)
No effect
No effect
Analog input reference
No effect
+24 Volt
Run Forward
Stop
Fast Stop
nd
deceleration ramp
Comments
Connect external motor
thermistor PTC type or
similar to digital input 3
Connect external motor
thermistor PTC type or
similar to digital input 3
Close digital input 3 to carry
out a fast stop (P-24),
provided P-05=0
Comments
Run and stop commands
given via the RS485 link and
Digital input 1 must be closed
for the drive to run.
Connect external motor
thermistor PTC type or
similar to digital input 3
Master Speed Ref - start and
stop controlled via RS485.
Keypad Speed Ref - drive
auto runs if digital input 1
closed, depending on P-31
setting
24